HTP PHR199-55C User Manual

Page 66

background image

66

LP- 325 REV. 3.21.14

F09

No flame detected

– Appliance

will make three attempts at

ignition before the control goes

into this lockout condition. Will

reset in 1 hour.

1. Watch the igniter through the observation window provided.
2. If there is

no spark, check the spark electrode for the proper ¼” gap.

3. Remove any corrosion from the spark electrode and flame rectifier probe.
4. If there is a spark but no flame, check the gas supply to the appliance.
5. If there is a flame, check the flame sensor.
6. Check any flue blockage or condensate blocks.

F10

Loss of flame signal

– The

appliance will relight 4 times

before the control goes into this
lockout condition. Will reset in 1

hour.

1. Monitor the gas pressure to the unit while in operation.

2. Assure that the flame is stable when lit.
3. Check to see if the green light on the display module is out while the appliance is running.
4. If the green light doesn’t come on or goes off during operation check the flame signal on the status
menu.
5. If the signal reads less than 1 microampere, clean the flame rectifier probe.
6. If the flame rectifier probe continues to read low, replace it.

F11F

False flame signal

– The

appliance will lock out if it

senses a flame signal when

there should be none present.

1. Turn the gas off to the unit at the service valve.
2. If the flame signal is still present replace the igniter.
3. If the flame signal is not present after turning off the gas supply, check the gas valve electrical
connection.
4. If there is no power to the gas valve, remove the valve and check for obstruction in the valve seat or
replace the gas valve.
5. Turn the gas on at the service valve after corrective action is taken.

F13

Combustion fan speed incorrect
– The appliance will lock out if it

senses that the fan speed is

less than 70% of expected rate

for more than 60 seconds.

1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.

pp

Parameters programmed

Press {S4} reset for at least 1 second.

F31

Program parameter error

Control must be re-programmed. If programming does not solve problem, control must be replaced.

Table 18 - NOTE: If you replace a part to remedy a fault, it is recommended that you cycle the unit at least three or four times
to assure the fault has been resolved.