D. status menu – HTP PHR199-55C User Manual
Page 60
60
LP- 325 REV. 3.21.14
5. Press
{S3}
a fifth time to access the final adjustment in this mode
– |t|, the Temperature Measurement in Fahrenheit to Celsius. To
change value, press either
{S1}
or
{S2}
to change the measurement from F (Fahrenheit) to C (Celsius).
D. STATUS MENU
Installers are also able to check the current status of the appliance parameters by pressing
{S4}
for 3 seconds. Once activated, the
display will show |d1| alternating value of the actual outlet temperature. Actual values are displayed for each function. To view the next
value, simply press the
{S4}
key.
Listed below are the values which can be displayed. These values cannot be changed. To exit this menu, simply press
{S3}
to resume
normal operation.
Function
– Value
To toggle between values press
{S1}
to go down and
{S4}
to go up. The first function you will see is:
|d1|
— Actual temperature from top sensor
|d2|
— Actual temperature from bottom sensor
|d3|
— PIONEER: Actual tank temperature if an indirect sensor is used.
*VERSA-FLAME: Displays the state of DHW demand
– 1 if flow switch is active (closed)
0 if flow switch is not active (open)
|d4|
— Not used
|d5|
— Actual temperature from the outdoor sensor |NC|.
|d6|
— Actual fan speed multiplied by 10 (Example: If fan speed displayed is |410| RPM x 10 = 4100 actual fan speed)
|d7|
— Actual ionization current read from flame rectification probe
|d8|
— Actual status of the central heating circulator Off = |0|, On = |1|.
|d9|
— Actual status of the indirect fired circulator Off = |0|, On = |1|.
*VERSA-FLAME: Status of the DHW module pump Off = |0|, On = |1|.
|d10|
— Actual status of bus communication |co| = connected, |nc| = not connected
|d11|
— Central heating set point
|d12|
— Power on hours in thousands (display will not read until 100 hrs.)
|d13|
— Total central heat hours in thousands (display will not read until 100 hrs.)
|d14|
— Total indirect/dhw hours in thousands (display will not read until 100 hrs.)
|d15|
— Passed ignition attempts in thousands
|d16|
— This function only becomes active when appliance is set as the Master. It allows the user to monitor the System Pump
connected to the Master Appliance (0 = Off, 1 = On) in a multiple appliance installation. Each appliance firing output percent is
displayed.
|P0| - Master Appliance - Alternating (0-100 Percentage firing rate)
|P1| - Follower Appliance #1
– Alternating (0-100 Percentage firing rate)
|P2| - Follower Appliance #2
– Alternating (0-100 Percentage firing rate)
|P3| - Follower Appliance #3
– Alternating (0-100 Percentage firing rate)
|P4| - Follower Appliance #4
– Alternating (0-100 Percentage firing rate)
|P5| - Follower Appliance #5
– Alternating (0-100 Percentage firing rate)
|P6| - Follower Appliance #6
– Alternating (0-100 Percentage firing rate)
|P7| - Follower Appliance #7
– Alternating (0-100 Percentage firing rate