HTP PHR199-55C User Manual
Page 16
16
LP- 325 REV. 3.21.14
dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and
bathroom exhausts, at maximum speed. Do not operate a summer exhaust fan. Close all fireplace dampers.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust the thermostat so the appliance will operate
continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle or
smoke from a cigarette.
6. After it has been determined that each appliance remaining connected to common venting system properly vents when tested as
outlined, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous condition of use.
7. Any improper operation of the common venting system should be corrected to conform to the National Fuel Gas Code, ANSI Z223.1.
When resizing any portion of the common venting system, the system should approach the minimum size as determined using the
appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z 223.1.