E. combustion system test mode, F. purge air from system, Part 10 – HTP PHR199-55C User Manual

Page 61: Programming the appliance, A. program access, B. program system settings, Part 10 – programming the appliance

background image

61

LP- 325 REV. 3.21.14


NOTE: If you toggle beyond parameters of connected appliances, the display will go into the next function value.

E. COMBUSTION SYSTEM TEST MODE

This function is intended to simplify the gas valve adjustment if needed. Listed below are the recommended limits on the appliance and
Combustion Settings. Automatic modulation does not take place when the controller is in Test mode, only temperature limitation based
on the Central Heating set point. The user may increase or decrease fan speed by pressing either

{S1}

or

{S2}

.


Press

{S2}

and

{S3}

together for 1 second to activate Test Mode. Once activated, you will see in the display

{Ser}

and the actual fan

speed. Measurement of combustion levels should always be taken at the highest and lowest fan speed. After 20 minutes, Test mode
stops automatically. Press

{S1}

and

{S2}

together for 1 second to exit Test Mode manually.

COMBUSTION SETTINGS ON ALL MODELS

Natural Gas

Propane LP

Fan Speed

Low

Ignition

High

Low

Ignition

High

Carbon Monoxide PPM

1

– 10

2 - 15

2

– 20

1

– 10

2 - 15

2

– 20

Carbon Dioxide (CO

2

)

8 - 10%

8

– 10%

8 - 10%

8 ½ - 10 ½%

8 ½ - 10 ½%

9 - 11%

Table 11

FAN SPEEDS

BTU

IGNITION

MIN

MAX

100,000

3000

2000

5700

130,000

3000

2000

7300

160,000

3000

2000

7450

199,000

3000

2000

9100

Table 12

F. PURGE AIR FROM SYSTEM

Manually Operating CH/DHW Pumps to Commission System
Disconnect the wires connected to the THERMOSTAT terminals of the field connection board. Apply power to the appliance. The
display will show the appliance water temperature. Press the

{S1}

and

{S3}

keys simultaneously and hold for 1 second. The display will

begin alternating between SEP and CH, and the central heating pump will come on. If you press

{S2}

again, the central heating pump

will shut off, the display will begin alternating between SEP and DH, and the DHW pump will come on. If the appliance is a cascade
master and you press

{S2}

again, the DHW pump will shut off, the display will begin alternating between SEP and Sh, and the system

pump will come on. You can use the

{S1}

and

{S2}

keys to toggle between running each pump in the system as required to help bleed

out all entrapped air. Some good indicators that air is removed include the absence of gurgling noises in the pipes and pump operation
becoming very quiet. Press

{S1}

and

{S2}

together at any time to return the control to normal operation.

PART 10 – PROGRAMMING THE APPLIANCE

The control allows the installer to set system limits and the heat curve for the Appliance. These system limits should not be changed by
the user. It is important to document your settings within this manual after you program the system parameters for future reference.

A. PROGRAM ACCESS

To start, press and hold

{S3}

and

{S4}

simultaneously for three seconds. You will notice the display change to

|000|

. Then, press and

hold

{S1}

until you see

|925|

. (If you go past

|925|

, you can use

{S2}

to decrease the number.) This is the pass code. To confirm that the

pass code is correct, press and hold the

{S3}

key for 1 second. If the pass code is entered incorrectly, the controller program function

will cancel and return to normal operation. If the code is entered correctly, the control will switch off the gas valve and purge fan while
showing a solid

- - -

in the display. The display will then show a |1| alternating to |de|. This first function verifies that the control will

function with the SuperStor Indirect Fired Water Appliance.

B. PROGRAM SYSTEM SETTINGS

Next you will have to press the

{S3}

key to move through each function. To increase or decrease a value, you will need to press either

the

{S1}

key or

{S2}

key to change the default values. If there is no key action for 1 minute, the display returns to normal operation.

Changes are effective immediately but not directly stored until the

{S4}

key is pressed down for 3 seconds then the new values are

stored. Listed below are the varieties of functions the installer can program.

DEFAULT

FUNCTION

VALUE

DESCRIPTION

1

|de|

N/A

2

149

o

F

N/A

3

180

o

F

PIONEER ONLY: Maximum set point for indirect water appliance temperature

(NOTE: Does not apply if used with mechanical control) - Range: 95

o

F

to 185

o

F