E. combustion system test mode, F. purge air from system, Part 10 – HTP PHR199-55C User Manual
Page 61: Programming the appliance, A. program access, B. program system settings, Part 10 – programming the appliance
61
LP- 325 REV. 3.21.14
NOTE: If you toggle beyond parameters of connected appliances, the display will go into the next function value.
E. COMBUSTION SYSTEM TEST MODE
This function is intended to simplify the gas valve adjustment if needed. Listed below are the recommended limits on the appliance and
Combustion Settings. Automatic modulation does not take place when the controller is in Test mode, only temperature limitation based
on the Central Heating set point. The user may increase or decrease fan speed by pressing either
{S1}
or
{S2}
.
Press
{S2}
and
{S3}
together for 1 second to activate Test Mode. Once activated, you will see in the display
{Ser}
and the actual fan
speed. Measurement of combustion levels should always be taken at the highest and lowest fan speed. After 20 minutes, Test mode
stops automatically. Press
{S1}
and
{S2}
together for 1 second to exit Test Mode manually.
COMBUSTION SETTINGS ON ALL MODELS
Natural Gas
Propane LP
Fan Speed
Low
Ignition
High
Low
Ignition
High
Carbon Monoxide PPM
1
– 10
2 - 15
2
– 20
1
– 10
2 - 15
2
– 20
Carbon Dioxide (CO
2
)
8 - 10%
8
– 10%
8 - 10%
8 ½ - 10 ½%
8 ½ - 10 ½%
9 - 11%
Table 11
FAN SPEEDS
BTU
IGNITION
MIN
MAX
100,000
3000
2000
5700
130,000
3000
2000
7300
160,000
3000
2000
7450
199,000
3000
2000
9100
Table 12
F. PURGE AIR FROM SYSTEM
Manually Operating CH/DHW Pumps to Commission System
Disconnect the wires connected to the THERMOSTAT terminals of the field connection board. Apply power to the appliance. The
display will show the appliance water temperature. Press the
{S1}
and
{S3}
keys simultaneously and hold for 1 second. The display will
begin alternating between SEP and CH, and the central heating pump will come on. If you press
{S2}
again, the central heating pump
will shut off, the display will begin alternating between SEP and DH, and the DHW pump will come on. If the appliance is a cascade
master and you press
{S2}
again, the DHW pump will shut off, the display will begin alternating between SEP and Sh, and the system
pump will come on. You can use the
{S1}
and
{S2}
keys to toggle between running each pump in the system as required to help bleed
out all entrapped air. Some good indicators that air is removed include the absence of gurgling noises in the pipes and pump operation
becoming very quiet. Press
{S1}
and
{S2}
together at any time to return the control to normal operation.
PART 10 – PROGRAMMING THE APPLIANCE
The control allows the installer to set system limits and the heat curve for the Appliance. These system limits should not be changed by
the user. It is important to document your settings within this manual after you program the system parameters for future reference.
A. PROGRAM ACCESS
To start, press and hold
{S3}
and
{S4}
simultaneously for three seconds. You will notice the display change to
|000|
. Then, press and
hold
{S1}
until you see
|925|
. (If you go past
|925|
, you can use
{S2}
to decrease the number.) This is the pass code. To confirm that the
pass code is correct, press and hold the
{S3}
key for 1 second. If the pass code is entered incorrectly, the controller program function
will cancel and return to normal operation. If the code is entered correctly, the control will switch off the gas valve and purge fan while
showing a solid
- - -
in the display. The display will then show a |1| alternating to |de|. This first function verifies that the control will
function with the SuperStor Indirect Fired Water Appliance.
B. PROGRAM SYSTEM SETTINGS
Next you will have to press the
{S3}
key to move through each function. To increase or decrease a value, you will need to press either
the
{S1}
key or
{S2}
key to change the default values. If there is no key action for 1 minute, the display returns to normal operation.
Changes are effective immediately but not directly stored until the
{S4}
key is pressed down for 3 seconds then the new values are
stored. Listed below are the varieties of functions the installer can program.
DEFAULT
FUNCTION
VALUE
DESCRIPTION
1
|de|
N/A
2
149
o
F
N/A
3
180
o
F
PIONEER ONLY: Maximum set point for indirect water appliance temperature
(NOTE: Does not apply if used with mechanical control) - Range: 95
o
F
to 185
o
F