Part 9, Start-up procedure, A. operating instructions – HTP PHR199-55C User Manual

Page 58: B. cascade system, Part 9 – start-up procedure

background image

58

LP- 325 REV. 3.21.14

2. Verify appliance and system are full of water and all system components are correctly set for operation.

3. Fill condensate trap with water.

4. Verify electrical connections are correct and securely attached.

5. Inspect exhaust vent and intake piping for signs of deterioration from corrosion, physical damage or sagging. Verify exhaust vent and
intake piping are intact and correctly installed per Venting section and local code.

PART 9 – START-UP PROCEDURE

FOR YOUR OWN SAFETY READ BEFORE OPERATING

1. This boiler does not have pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the
burner by hand.

2. BEFORE OPERATING: smell all around the boiler area for gas. Be sure to smell next to the floor because some gas is heavier than
air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any boiler.

Do not touch any electric switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor's phone. Follow the gas suppliers' instructions.

If you cannot reach your gas supplier, call the fire department.

Turn off gas shutoff valve (located outside of the boiler) so that the handle is crosswise to the gas pipe. If the handle will not
turn by hand, don't try to force or repair it, call a qualified service technician. Force or attempted repair may result in a fire or
explosion.


4. Do not use this boiler if any part has been under water. Immediately call a qualified service technician to inspect the boiler and to
replace any part of the control system and any gas control that has been damaged.

5. The boiler shall be installed so the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during
boiler operation and service (circulator replacement, condensate trap, control replacement, etc.)

Failure to follow these instructions could result in property damage, serious personal injury, or death.

A. OPERATING INSTRUCTIONS

If you smell gas, STOP. Follow listed safety instructions. If you do not smell gas, follow the next steps.


1. Turn on all electrical power to the appliance.

2. Adjust the temperature set point of the appliance if desired. The factory default setting is 180

o

F. If changes are necessary, follow,

“Adjusting the Set point”, below.

3. Set the thermostat to create a demand for heat.

4. If the appliance fails to start, refer to the Troubleshooting section in the back of this manual.

B. CASCADE SYSTEM

1. If the appliance is used alone, skip this section.

2. Programming the Master Appliance

a. Make sure there is no demand for heat being supplied to the appliance.
b. Apply power to the appliance.
c. Enter the Installer Menu following instructions in Part 10 of this manual.
d. Verify that parameter 15 is set to 0. This makes the Master Appliance address 0.
NOTE: The Master Appliance MUST be addressed as 0.
e. Set parameter 23 from 0 to 1.

f. Exit the installer menu.


These settings designate this appliance as the Master Appliance.