beautypg.com

Kasco Marine Robust-Aire User Manual

Page 8

background image

8

from

compressor

to

diffuser

3/8” or 5/8”

tubing

RM1

to

diffusers

valve

box

from

compressor

RM2

RM3

from

compressor

to

diffusers

valve

box

an area by shore to bury the included valve box. An

area at least 18” wide by 25” long x 13” deep will be

needed. Dig the area deeper and add crushed rock to

allow for drainage.

CAUTION: In northern climates where the ground

may freeze during the winter, be sure there are no

peaks and valleys in the PVC air line. Condensation

in the air line may freeze and can block the flow of

air to your diffuser and can cause damage to your

compressor.

For RA1 – RA3 systems, a single trench is all that is

required.

For RA4 – RA6 systems, either a single trench or two

separate trenches may be required depending on pond

size and diffuser placement locations.

Connect brass barb fitting to PVC adapter, applying

thread sealant to male threads on PVC adapter.

Connect barb fitting to rubber hose lead from

compressor and secure with hose clamp.

Connect PVC adapter and PVC pipe with primer and

glue. Add PVC pipe sections as needed to reach the

location of the remote manifold.

Prime and glue supplied manifold assembly to the end

of the PVC pipe run. Install 3/8” barb fittings or 5/8”

barb fittings depending on size of SureSink™ tubing

being run from the manifold to each diffuser. Apply

thread sealant to male threads of barb fittings. Attach

SureSink™ tubing to barb fittings and secure with

hose clamp.

When applicable, place valve box over manifold

assembly and fill in around box and entire length of

trench with the excavated dirt. The lid of the valve

box should be flush with the top of the ground surface.

When system has been completely installed, use the

valves (not provided on single diffuser systems) to

balance the flow to each diffuser.