Commissioning, Finding detectors and selecting power mode – Fire Fighting Enterprises FIRERAY 5000 4-Head (Legacy) User Manual
Page 8

Finding Detectors and Selecting Power Mode
Commissioning
3. Find Detectors
60 seconds
• Press tick to enable ‘Found’ Detectors
• Any unused Detector channels are switched
off
• Press
to re-scan if number is incorrect
Menu Navigation
• All functions can be performed in ‘Lo A’ mode (default)
(10, 12, 14 or 16 mA for 1, 2 ,3 or 4 Detectors found)
• The system will default to ‘Lo A’ mode when power is
applied
• Select ‘Hi A’ (50mA) to enable faster beam movement
during Auto-Align, Hand Align and Laser Targeting
• After installation, set the system back to ‘Lo A’
4. Select Power Mode
1. Use
to move between
icons in the Engineering Menu, to
highlight the icon shown
3. Use
to move to
required item
2. Press
to select
This will be the number of
Detectors found
4. Use
to
change selection
5. Press
to accept
Press
to cancel
• ‘Find’ is
automatically
displayed the first
time this process
is run. ‘Find’ can
also be accessed
in the System
Controller settings
menu
8