Approval Information
Territory-Specific Approval Information
European Approval Information
Complies with EN54-12 for sensitivity levels between 25%
and 35% with a maximum delay to fire of 20 seconds.
UL Approval Information
UL File Number: S3417
0832
Fire Fighting Enterprises Ltd, 9 Hunting Gate, Hitchin,
SG4 0TJ, UK
07
0832-CPD-0565
EN54-12
Line Detector using an Optical Beam
Fire Safety
Documentation: See doc. 0044-034
Distance between
Detector and Reflector
Fire Threshold
Range
8
—
10m (26.2
—
32.8ft)
10
—
18%
10
—
15m (32.8
—
49.2ft)
15
—
25%
15
—
22m (49.2
—
72.2ft)
15
—
35%
22
—
40m (72.2
—
131.2ft)
25
—
50%
40
—
60m (131.2
—
196.8ft)
35
—
50%
60
—
100m (196.8
—
328.1ft)
50%
All installations should comply with NFPA72
Document Number: 0044-034-01
30
0044-034-01 - THESEUS UG - ENGLISH:0044-003-01 User Guide.qxd 23/06/2009 08:39 Page 30
Complies with EN54-12 for sensitivity levels between 25%
and 35% with a maximum delay to fire of 20 seconds.