0 meter installation, 1 mounting the meter, 2 main power board connections – E-Mon E20-6003200J-D-KIT User Manual
Page 8
CLASS 2000 METER
62-0389-05
8
4.0 METER INSTALLATION
4.1 Mounting the Meter
Using the appropriate sized mounting hardware, fasten the Class 2000 meter
enclosure to the selected mounting surface. The four mounting holes are centered
6.75” H x 4” W. The mounting hole spacing is identical for either the UL Type 1 or
NEMA 4X enclosure.
NOTE: Only the NEMA 4X plastic enclosed unit is suitable for outdoor environ-
mental conditions. Units housed in UL Type 1 JIC steel enclosures must
only be installed in indoor environments where it will not be affected by
the elements, such as moisture and extreme temperatures.
Fig. 3. Enclosure Dimensions.
4.2 Main Power Board Connections
1. Install a temporary ground for ESD (Electrostatic Discharge) protection. With all
circuits de-energized, connect a temporary protective earth ground connection
for ESD protection. Prior to performing any unit wiring, be sure to discharge any
static on your person.
2. Install the Class 2000 Protective Earth Ground. Connect an earth ground wire to
the Class 2000 protective earth ground terminal screw located on the right side
of the line voltage terminal block. After installing the protective earth ground wire,
securely fasten the protective earth ground screw.
3 (76)
7-1/2
(191)
M33627
6 (152)
4 (102)
6-3/4
(171)
- E20-6001600J-D-KIT E20-600800-J-D-KIT E20-600400-J-D-KIT E20-600200-J-D-KIT E20-600100-J-D-KIT E20-6003200JKIT E20-6001600JKIT E20-600800-JKIT E20-600400-JKIT E20-600200-JKIT E20-600100-JKIT E20-4803200J-D-KIT E20-4801600J-D-KIT E20-480800-J-D-KIT E20-480400-J-D-KIT E20-480200-J-D-KIT E20-480100-J-D-KIT E20-4803200JKIT E20-4801600JKIT E20-480800-JKIT E20-480400-JKIT E20-480200-JKIT E20-480100-JKIT E20-2083200J-D-KIT E20-2081600J-D-KIT E20-208800-J-D-KIT E20-208400-J-D-KIT E20-208200-J-D-KIT E20-208100-J-D-KIT E20-2083200JKIT E20-2081600JKIT E20-208800-JKIT E20-208400-JKIT E20-208200-JKIT E20-208100-JKIT