Repeat the process for the B sensor gray plug. Connect only the B sensor plug to the B
phase current senor input terminal with the correct polarity (white to white and black to
black) the sensor error remains clears then the B sensor input leads polarity is correct
Fig. 11. Error LED
If the Error LED illuminates then reverse the input leads for B sensor by putting the
white leads on the black input and the black leads on the white input, (swapped
polarity). If it clears, the Error LED then tag as the B phase plug and take the gray plug
off the input marking them as B and note polarity to identify them later.
POWER LED
PULSE LED
ERROR LED
M34957
This manual is related to the following products:
- E20-6001600J-D-KIT E20-600800-J-D-KIT E20-600400-J-D-KIT E20-600200-J-D-KIT E20-600100-J-D-KIT E20-6003200JKIT E20-6001600JKIT E20-600800-JKIT E20-600400-JKIT E20-600200-JKIT E20-600100-JKIT E20-4803200J-D-KIT E20-4801600J-D-KIT E20-480800-J-D-KIT E20-480400-J-D-KIT E20-480200-J-D-KIT E20-480100-J-D-KIT E20-4803200JKIT E20-4801600JKIT E20-480800-JKIT E20-480400-JKIT E20-480200-JKIT E20-480100-JKIT E20-2083200J-D-KIT E20-2081600J-D-KIT E20-208800-J-D-KIT E20-208400-J-D-KIT E20-208200-J-D-KIT E20-208100-J-D-KIT E20-2083200JKIT E20-2081600JKIT E20-208800-JKIT E20-208400-JKIT E20-208200-JKIT E20-208100-JKIT