CLASS 2000 METER

62-0389-05

18

Repeat the process for the C sensor gray plug. With only the C sensor plug connected

if the sensor error remains clear then the C sensor input and the polarity is correct (see

Fig. 12).

Fig. 12. The green power LED blinks this is normal.

If the Error LED illuminates disconnect the plug and reverse the wires for C sensor by

putting the white leads on the black input and the black leads on the white input,

(swapped polarity). When Error LED is clear leave the sensor C plug plugged into “C”

phase current sensor input C.

Reconnect sensor A and sensor B plugs as you had previously identified them for

phase and polarity.

The error should now be clear.

Class 2000 meters may only use one or two sensors depending on the applications.

Please see the appropriate installation manual for wiring configurations in these type

applications. “Check Install” message will always be present in single phase

applications on a Class 2000 meter and will not affect the meter accuracy.

POWER LED

PULSE LED

ERROR LED