Repeat the process for the C sensor gray plug. With only the C sensor plug connected
if the sensor error remains clear then the C sensor input and the polarity is correct (see
Fig. 12).
Fig. 12. The green power LED blinks this is normal.
If the Error LED illuminates disconnect the plug and reverse the wires for C sensor by
putting the white leads on the black input and the black leads on the white input,
(swapped polarity). When Error LED is clear leave the sensor C plug plugged into “C”
phase current sensor input C.
Reconnect sensor A and sensor B plugs as you had previously identified them for
phase and polarity.
The error should now be clear.
Class 2000 meters may only use one or two sensors depending on the applications.
Please see the appropriate installation manual for wiring configurations in these type
applications. “Check Install” message will always be present in single phase
applications on a Class 2000 meter and will not affect the meter accuracy.
POWER LED
PULSE LED
ERROR LED
M34958
- E20-6001600J-D-KIT E20-600800-J-D-KIT E20-600400-J-D-KIT E20-600200-J-D-KIT E20-600100-J-D-KIT E20-6003200JKIT E20-6001600JKIT E20-600800-JKIT E20-600400-JKIT E20-600200-JKIT E20-600100-JKIT E20-4803200J-D-KIT E20-4801600J-D-KIT E20-480800-J-D-KIT E20-480400-J-D-KIT E20-480200-J-D-KIT E20-480100-J-D-KIT E20-4803200JKIT E20-4801600JKIT E20-480800-JKIT E20-480400-JKIT E20-480200-JKIT E20-480100-JKIT E20-2083200J-D-KIT E20-2081600J-D-KIT E20-208800-J-D-KIT E20-208400-J-D-KIT E20-208200-J-D-KIT E20-208100-J-D-KIT E20-2083200JKIT E20-2081600JKIT E20-208800-JKIT E20-208400-JKIT E20-208200-JKIT E20-208100-JKIT