beautypg.com

E-Mon E20-6003200J-D-KIT User Manual

Page 16

background image

CLASS 2000 METER

62-0389-05

16

1. Disconnect the Gray current sensor plugs for current sensor B and C phase

inputs (see Fig. 10).

Fig. 10. Error LED

With only the A sensor wires connected to the sensor A input verify if the error LED is

clear (Green LED is off).

If Error LED is clear then the A sensor input leads polarity is correct.

If the Error LED does not clear, then disconnect the gray plug and reverse the input

leads for A sensor by putting the white leads on the black input and the black leads on

the white input, (swapped polarity). If it clears, the “Sensor Error” then mark this pair

with a piece of masking tape as the A sensor and note polarity. Next disconnect the

gray plug for the A input. Marking them with tape as A and noting the polarity.

POWER LED

PULSE LED

ERROR LED

M34955