10.0 TROUBLESHOOTING GUIDE

The Class 2000 kWh/Demand meter is calibrated and tested at the factory before

being packaged and shipped. If installed properly and in accordance with these

installation instructions, your Class 2000 meter should provide years of trouble free

service. If the meter should not function, the following guide will assist in

troubleshooting the installation.

NOTE: If you still need assistance after performing the above troubleshooting

procedures, do not remove the unit. Before removing the unit, contact

E-Mon’s technical support department at (800) 334-3666, our support

experts will assist you in detailed troubleshooting of the meter installa-

tion and assist you in getting the unit operating correctly

Problem

Procedure to follow

1. Display window is blank.

Check wiring to voltage terminals.
Check circuit breakers or fuses.
Verify that the power is turned on.
Test source for correct voltage.

2. Display shows incomplete figures or

numbers other than zeros when power is

turned on.

Press RESET button located on door

inside meter enclosure (5 sec.)

3. Display reading all zeros (00000000)

Determine if load is sufficient to update

the display.
Check RESET button to ensure there are

no wires or other objects pressing against

it when the door is closed.
Check the current sensors for installation

and polarity.
Be sure the current and voltage inputs

have the proper phase relationship.
Check wiring to voltage terminals.
Check circuit breaker or fuses.
Test source for correct voltage.

4. Display reads only a fraction of

consumption

Check the supply voltage to be sure that it

is on continuously 24 hrs/day.
Check the current sensors for installation

and polarity.
Check sensor wiring to the terminal strip

in meter (color coding B & W.)