This boiler is equipped with an
ignition device which automatically
lights the burner. Do not try to light
burner by hand.
13. Once combustion is checked and verifi ed with a combustion analyzer
place the control back into automatic mode and check all boiler safeties.
TABLE 8 - VERIFICATION OF IGNITION ENRICHMENT
Model
Size
Spring
Color
Enrichment Valve Outlet Pressure
1000
silver
4 - 5”w.c.
1500
brown
2.5 - 3.8” w.c.
2000
brown
2.5 - 3.8” w.c.
TABLE 9 - VERIFICATION OF COMBUSTION SETTING
Low Fire
High Fire
O2
5.0 - 5.4%
3.0 - 5.5%
CO2
8.7 - 9.0%
8.0 - 10.0%
Turndown
EDR-1500 and EDR-2000 boilers leave the factory with a default setting of 5:1
turndown; however, 8:1 may be allowable if site conditions permit. EDR-1000
boilers have a default setting of 10:1 turndown.
Please consult a factory-trained representative for guidance.