Installation – Fulton Endura (EDR) Condensing Hydronic Boiler User Manual

Page 10

background image

© The Fulton Companies 2014

INSTALLATION

EDR-IOM-2014-0318

SECTION 2

2-4

TABLE 1 - BOILER DIMENSIONS AND OPERATING REQUIREMENTS

FIGURE 1 - VIEWS OF ENDURA HYDRONIC BOILER

Alternate gas pressure arrangements may apply. Please verify gas pressure ratings for your boiler by viewing the boiler name plate.

Typical 120 VAC controls allow for a +10% and a -15% voltage fl uctuation. Voltages lower than 120 V can result in slightly decreased available output.

*Standard confi gurations. Alternate voltages may be available as an option; please consult factory.

Note: All dimensions are approximate and are subject to change without notice.

MODEL EDR

1000

1500

2000

Input Million BTU/Hr
kW

1.0

293

1.5

411

2.0

549

Fuel Cons. @ rated cap. (Nat. Gas)
FT3/Hr
M3/Hr

1000

28.32

1500

42.5

2000

56.7

Output at AHRI Test Condition
BHP
KCal/h

28.4

239,396

41.9

353,424

56

472,240

Electrical Req. (Amps)*
120V, 60Hz, 1 Phase

10

20

20

Water Content Gal
Liters

50

189

104
394

102
386

Dry Weight LBS
KG

1430

649

2260
1025

2360
1071

Operating Weight LBS
KG

1848

838

3128
1419

3210
1456

MODEL EDR

1000

1500

2000

A. Boiler Width IN
CM

28
72

33.9

86

33.9

86

B. Overall Boiler Height IN
CM

68

172.7

80

203.2

80

203.2

C. Overall Boiler Depth IN
CM

49.75
126.4

60.6

153.8

60.6

153.8

D. Flue Outlet Diameter IN
CM

6

15.2

6

15.2

8

15.2

E. Water Inlet/Outlet Diameter IN
CM

2

5.08

4

10.2

4

10.2

F. Min. Clearance (top) IN
CM

18
46

18
46

18
46

G. Air Inlet Diameter (top access) IN
CM

6

15.25

8

20.3

8

20.3

Min. Clearance (sides) IN
CM

1

2.5

1

2.5

1

2.5

FRONT VIEW

RIGHT SIDE VIEW

BACK VIEW

TOP VIEW

B

D

E

G

E

C

F

A