Installation – Fulton Endura (EDR) Condensing Hydronic Boiler User Manual
Page 10

© The Fulton Companies 2014
INSTALLATION
EDR-IOM-2014-0318
SECTION 2
2-4
TABLE 1 - BOILER DIMENSIONS AND OPERATING REQUIREMENTS
FIGURE 1 - VIEWS OF ENDURA HYDRONIC BOILER
Alternate gas pressure arrangements may apply. Please verify gas pressure ratings for your boiler by viewing the boiler name plate.
Typical 120 VAC controls allow for a +10% and a -15% voltage fl uctuation. Voltages lower than 120 V can result in slightly decreased available output.
*Standard confi gurations. Alternate voltages may be available as an option; please consult factory.
Note: All dimensions are approximate and are subject to change without notice.
MODEL EDR
1000
1500
2000
Input Million BTU/Hr
kW
1.0
293
1.5
411
2.0
549
Fuel Cons. @ rated cap. (Nat. Gas)
FT3/Hr
M3/Hr
1000
28.32
1500
42.5
2000
56.7
Output at AHRI Test Condition
BHP
KCal/h
28.4
239,396
41.9
353,424
56
472,240
Electrical Req. (Amps)*
120V, 60Hz, 1 Phase
10
20
20
Water Content Gal
Liters
50
189
104
394
102
386
Dry Weight LBS
KG
1430
649
2260
1025
2360
1071
Operating Weight LBS
KG
1848
838
3128
1419
3210
1456
MODEL EDR
1000
1500
2000
A. Boiler Width IN
CM
28
72
33.9
86
33.9
86
B. Overall Boiler Height IN
CM
68
172.7
80
203.2
80
203.2
C. Overall Boiler Depth IN
CM
49.75
126.4
60.6
153.8
60.6
153.8
D. Flue Outlet Diameter IN
CM
6
15.2
6
15.2
8
15.2
E. Water Inlet/Outlet Diameter IN
CM
2
5.08
4
10.2
4
10.2
F. Min. Clearance (top) IN
CM
18
46
18
46
18
46
G. Air Inlet Diameter (top access) IN
CM
6
15.25
8
20.3
8
20.3
Min. Clearance (sides) IN
CM
1
2.5
1
2.5
1
2.5
FRONT VIEW
RIGHT SIDE VIEW
BACK VIEW
TOP VIEW
B
D
E
G
E
C
F
A