beautypg.com

Installation, Install ph neutralization kit – Fulton Endura (EDR) Condensing Hydronic Boiler User Manual

Page 20

background image

© The Fulton Companies 2014

INSTALLATION

EDR-IOM-2014-0318

SECTION 2

2-14

are not supplied with the boiler).

5. All piping (Figure 4) must be galvanized or stainless

steel, and be free of leaks. Copper, carbon steel/iron
pipe, PVC or CPVC are not acceptable.

6. Connect 1 inch (25.4 mm) condensate drain(s) (at the

rear of the boiler), to the 1 inch (25.4 mm) inlet at the
base of the drain tank. The header must be at least 5.5
inches (14.2 cm) below the condensate outlet of the
individual boiler, and must remain fl ooded - achieved
by ensuring it is at least 5.5 inches (14.2 cm) below the
outlet of the condensate drain trap.

7. Connect the 1.5 inch (38.1 mm) drain outlet to an

appropriate waste line following applicable codes. The
1.5 inch (38.1 mm) drain connection on the drain tank
must be the highest point prior to going to the drain.
Failure to keep drain piping lower than this point will
result in overfl ow of the drain tank. Slope the drain
pipe away at a minimum pitch of 1 inch (25.4 mm) for
every 12 feet (3.65 m).

8. (U.S.

Only)

Attach a ¼” water supply to the

compression fi tting on the fl oat. The water line must
be connected to an uninterruptible supply. Fulton

recommends connecting it before the “fast fi ll” valve
to the boiler supply but after the back fl ow preventer
to avoid contamination of a potable water supply.
Maximum allowable water pressure to the compression
fi tting is 100 PSI (689.5 kPa).

Install pH Neutralization Kit

The pH Neutralization Kit is a Fulton-provided kit designed to
bring the pH level of the boiler’s condensate to a neutral level.
It is not a replacement or alternative for the Condensate Drain
Trap. See Figure 5.

Adhere to the following for pH Kit installation:

1. Use stainless or galvanized pipe and fi ttings to connect

condensate drain to kit.

2. Connect kit downstream of Condensate Drain Trap. See

Figure 6.

3. Pipe outlet to appropriate drain.

4. Check condensate pH periodically.

TOP VIEW

30 3/8

[771]

12 1/2

[318]

3 13/16

[97]

(TYP.)

FRONT VIEW

1 1/2" PLASTIC FITTING
CONNECTION TO DRAIN

1" NPT

CONNECTION

TO BOILER

10 3/4

[273]

11 1/4
[286]

ISOMETRIC VIEW

2

3

1

4

3

1. Neutralizer Kit with Magnesium Oxide

2. Condensate Drain Kit Assembly

3. 1 1/2” by 3” NPT Stainless or Galvanized Nipple

4. 1 1/2” Stainless or Galvanized Union

FIGURE 6 - FIELD CONNECTIONS FOR CONDENSATE DRAIN TO PH NEUTRALIZATION TANK