Installation, The fulton companies 2014, Figure 9 - wall penetration details – Fulton Endura (EDR) Condensing Hydronic Boiler User Manual
Page 28: Endura hydronic boiler

© The Fulton Companies 2014
INSTALLATION
EDR-IOM-2014-0318
SECTION 2
2-22
FIGURE 9 - WALL PENETRATION DETAILS
ENDURA
HYDRONIC
BOILER
COMBUSTIBLE WALL
PENETRATION DETAIL
NON-COMBUSTIBLE
WALL PENETRATION
PARTIAL DETAIL
AL29-4C or 316L STAINLESS STEEL
HIGH TEMPERATURE
EXHAUST PIPE & FITTINGS
INSTALL SUPPORT STRAP AT
5 FT / 150 CM HORIZONTAL
INTERVALS AND AT
INTERMEDIATE ELBOWS
(SPRING HANGERS ARE
RECOMMENDED)
10" PVC PIPE (U.S. ONLY)
COUPLING
REQUIRED AIR
SPACE CLEARANCE
COMBUSTIBLE WALL
WALL TERMINATION
( WITH SCREEN )
6 IN / 15 CM
MIN. / MAX. WALL THICKNESS
( 3 1/4 IN. - 20 IN. )
( 8.255 CM - 50.8 CM )
DO NOT PLACE INSULATION IN
REQUIRED AIR SPACE CLEARANCE
BAND SUPPORT
COLLAR
(TYP EACH SIDE)
SCREENED
TERMINATION
WALL TERMINATION
( WITH SCREEN )
1/4" TAPPING FOR WATER
100 PSI MAXIMUM (U.S. ONLY)
90° PVC ELBOW
SCREENED AIR INLET
EXHAUST PIPE
WALL PENETRATION
48 IN. / 122 CM.
48 IN. / 122 CM.
(MINIMUM)
AIR INTAKE
WALL PENETRATION
LOCATE INTAKE
UPWIND OF
EXHAUST PIPING
AIR INTAKE & EXHAUST PIPES WALL PENETRATION CLEARANCES
CAUTION:
AIR INTAKE AND EXHAUST TERMINATION SHOULD BE
SEPARATED AS FAR AS POSSIBLE TO PREVENT FLUE GAS
RECIRCULATION DURING DIFFERENT WIND CONDITIONS
NOTE:
MAINTAIN MINIMUM 9"/22.86 CM AIR SPACE
CLEARANCES TO COMBUSTABLES, WIRES AND INSULATION
AIR INLET
4 FT / 122 CM ( MINIMUM )
BETWEEN INLET & EXHAUST
OPENING ( SEE BELOW )
AIR INTAKE AND EXHAUST
TERMINATION SHOULD BE
SEPERATED AS FAR AS POSSIBLE
TO PREVENT FLUE GAS
RECIRCULATION DURING
DIFFERENT WIND CONDITIONS.
OPENING 1 FT / 30 CM ( MIN )
ABOVE NORMALLY EXPECTED
SNOW ACCUMULATION LEVEL
OPENING 1 FT / 30 CM ( MIN )
ABOVE NORMALLY EXPECTED
SNOW ACCUMULATION LEVEL
PVC
90° ELBOW
RISE TO RUN: 1/4" PER FOOT
EXHAUST