beautypg.com

Installation, Detail a – Fulton Endura (EDR) Condensing Hydronic Boiler User Manual

Page 18

background image

© The Fulton Companies 2014

INSTALLATION

EDR-IOM-2014-0318

SECTION 2

2-12

FIGURE 4 - CONDENSATE DRAIN PIPING FOR ENDURA BOILERS

Figure 4 Notes:

 Header must be level or slightly pitched toward the drain.

 Header material to be galvanized steel or 316L stainless.

 Header should be taken to the lowest point possible and

maintain a minimum 5.5 inch (14.2 cm) drop from 1.5 inch
(38.1 mm) condensate drain kit/trap outlet. See Detail A.

 1.5 inch (38.1 mm) condensate drain kit/trap outlet is never

to be above 1 inch boiler condensate outlet.

 For multiple boiler installation, maintain and minimum pipe

size of 1 inch (25.4 mm) for the header piping.

 The maximum capacity to attach per condensate drain kit is

12 MMBH total.

Detail A

0.25” (U.S.) TAPPING
PROVIDED FOR WATER
CONNECTION TO MAINTAIN
WATER SEAL

5.5 INCH (14.2 CM)
MINIMUM

REAR VIEW

Detail A

Condensate

Drain Kit