CONTROL BOARD SETUP
Viking Heater
The operator has an integrated heater. Activate this feature when the operator is used in
application temperatures down to -20°F (-29°C).
HEATER
CLS ON
To set the heater to turn on at the Close Limit:
1. Use the “Diagnose” button to scroll through the LCD
menu to “HEATER CLS”
2. Press and hold the “Stop” button on the control board.
3. Press and release the “Diagnose” button to turn this
feature ON and OFF.
NOTE:
If the application requires the gate to be held open for any reason, set the HEATER
ON for both limit positions.
!
IMPORTANT:
A POSITIVE STOP
must be used on the gate at the limit position(s) the
HEATER has been set for.
HEATER
OPN ON
To set the heater to turn on at the Open Limit:
1. Use the “Diagnose” button to scroll through the LCD
menu to “HEATER OPN”
2. Perform steps 2-3 as described above.