Table 3-1: Interface Current Consumption

Figure 3-1 shows the PSU-101 to IMF-3 wiring possibilities.

Figure 3-1: PSU-101 to IMF-3 Wiring

IMF-102 Interface Module Frame

The IMF-102 interface frame has an internal power supply and a
rear-panel connector to provide redundant power. The IMF-102
requires 90 to 250 VAC with a maximum dissipation of 20 watts.

DIF-102 Interface Module Frame

The DIF-102 interface frame is powered by one or two (for
redundancy) external AC mains to 24 VDC power supplies via locking
DIN connectors on the DIF-102 rear panel. All other voltages are
derived directly or indirectly from the input 24 VDC on the DIG-2 front
and rear cards.

The DIF-102 frame has a PSU fail-alarm output provided by Form C
relay change-over contacts made available on a 9-way make D
connector on the DIF-102 rear panel.

Component

Average

Current

Maximum

IMF-3 Frame

0.20 A

0.20 A

CCI-22

0.00 A

0.00 A

FOR-22

0.07 A

0.15 A

TEL-14

0.28 A

0.37 A

RLY-6

0.10 A

0.15 A

GPI-6

0.02 A

0.02 A

PSU-101