ST100 Series Foundation Fieldbus
10
Fluid Components International LLC
SECONDARY_VALUE parameter
This parameter makes available to the AI block the temperature value of the ST100. There are two valid engineering units associated with
this parameter, ºC and ºF
TERTIARY_VALUE parameter
This parameter makes available to the AI block the Totalizer value of the ST100. This is an optional parameter that can be turned “ON” or
“OFF”. It is associated with the volumetric flow and the mass flow. The units are set by the flow units selected.
QUATERNARY_VALUE parameter
This parameter makes available to the AI block the pressure value of the ST100. This is an optional parameter that can be activated when A
flow sensor is connected to the ST100. The engineering units associated with this variable are PSIG, in H2Og, bar (g), Kpa(g), cm H2O g, in Hg
, KpaA, mm Hg.
Engineering units can be viewed through this block.
ST100 Process Data Transducer Block
The table below summarizes the ST100 Process Data Transducer Block.
INDEX
PARAMETER
DATA TYPE (LENGTH)
INITIAL VALUE
DESCRIPTION
0
BLOCK OBJECT
DS-64
1
ST_REV
Unsigned16
0
2
TAG_DESC
Octet String
spaces
3
STRATEGY
Unsigned16
0
4
ALERT_KEY
Unsigned8
0
5
MODE_BLK
DS-69
0
6
BLOCK_ERR
Bit String
0
7
UPDATE_EVT
DS-73
8
BLOCK_ALM
DS-72
9
TRANSDUCER_DIRECTORY
Unsigned16
0
10
TRANSDUCER_TYPE
Unsigned16
65534
11
XD_ERROR
Unsigned8
0
12
COLLECTION_DIRECTORY
Unsigned32
13
PRIMARY_VALUE
DS-65
0; 0.0
ST100 Flow Variable
14
PRIMARY_VALUE_UNIT
Unsigned16
0
ST 100 Flow Units
15
SECONDARY_VALUE
DS-65
0; 0.0
ST 100 Temperature Variable
16
SECONDARY_VALUE_UNIT
Unsigned16
0
ST100 Temperature Variable
17
TERTIARY_VALUE
DS-65
0; 0.0
ST 100 Totalizer Variable
18
TERTIARY_VALUE_UNIT
Unsigned16
0
ST100 Totalizer Units
19
QUATERNARY_VALUE
DS-65
0; 0.0
ST100 Pressure Variable
20
QUATERNARY_VALUE_UNIT
Unsigned16
0
ST 100 Pressure Units