Table 3 – Fluid Components International OEM Flow Meter User Manual
Page 3
OEM MASS FLOW
FLUID COMPONENTS INTERNATIONAL LLC
The top level of the menu is shown below. Enter the large letter in the tables below to activate a command.
Doc. No. 06EN003329 Rev. B
“Z” Flow Units Set-up and Scaling
Units
Select
E=English
M=Metric
Select
F= SFPS
M=SMPS
or
C = SCFM
N = NCMH
or
H = SCFH
O = NCMM
or
L = LBS/H
K = KG/H
For Volumetric or Mass Flow
Select
R = Round pipe or duct
or
S = Square duct
Set
Diameter or Wide X High (in inches or mm)
Set
Max = Maximum flow rate (span)
Set
Zero = Minimum flow rate (zero)
Table 3
“V” Output Configuration Set-up
Analog out
Select
1
2
3
4
4-20mA out
Flow
Flow
Temp
Temp
0-10 Vout
Temp
Flow
Flow
Temp
Pulse out
Select
1
2
3
4
Source out
Pulse
Pulse
Alarm0
Alarm0
Set
Factor
Factor
Set pt.0
Set pt.0
Set
Period
Period
State0
State0
Set
State0
State0
Sink
Pulse
Alarm1
Pulse
Alarm1
Set
Set pt.1
Factor
Set pt.1
Set
State1
State1
Period
State1
State1
Table 4
Table 2
User may exit command at any time entering
“Q” [ENTER] in menus: D, K, L, V, W, or Z.
C
Calibration Information
Display only: A/D, Delta-R, Ref-R data values
D
Diagnostics
Display only: Check-out of functional conditions
K
Factory Calibration Settings
Display only: Cal. parameters, i.e. linearization
and temperature compensation coefficients.
L
Calibrate Outputs
Factory Access Only
Y
Command Line Interface Factory Access Only
R
Factory Reset
Replaces user data with factory calibration data
Diagnostics and Factory Settings
Analog out
Output Mode
Selected
4-20mA: Flow
0-10V: Temp
Change? (Y/N)>
4-20mA: Flow
0-10V: Temp
Enter 1 to make
the selection__
4-20mA: Flow
0-10V: Flow
Enter 2 to make
the selection__
4-20mA: Temp
0-10V: Flow
Enter 3 to make
the selection__
4-20mA: Temp
0-10V: Temp
Enter 4 to make
the selection__
Display comes up to last setting saved
and stays for 2 seconds.
If N or [ENTER], proceed to Pulse out.
If Y, display moves to selection
options and asks for confirmation. If
you miss the option, select [Enter]
repeatedly to loop around.
Pulse out
Pulse Out
Selected
Source: Pulse
Sink: Pulse
Change? (Y/N)>
Source: Pulse
Sink: Pulse
Enter 1 to make
the selection #__
Source: Pulse
Sink: Alarm1
Enter 2 to make
the selection #__
Source: Alarm0
Sink: Pulse
Enter 3 to make
the selection #__
Source: Alarm0
Sink: Alarm1
Enter 4 to make
the selection #__
PFactor: 1.000
Change? (Y/N)>
if yes
Enter new factor: ____
Sample Period: 1 second
Change? (Y/N)>
if yes
Enter new Sample Period: ____
If alarm is a selected output
Set point1: 000
Set points are in the
same units as the flow
or temp.
Change? (Y/N)>
if yes
Enter new set point: ____
Resume normal operation
Source state: 0
Change to 1?>
Sink state: 1
Change to 0?>
T
Normal Operation Mode
All outputs active
F
K Factor (1 is default)
Z
Flow Units Set-up
Select flow units (4 English, 4 Metric),
Pipe diameter and span/zero settings
W Totalizer Mode
Disable/Enable internal totalizer
V
Output Configuration Selection
Select one of four output configurations: pulse
and/or alarm, plus pulse factor and/or set point
N
Warm Reset
Re-initialize instrument without removing power
Table 1
Customer Settings
This page is subject to proprietary rights statement on last page
Note: Changing units requires rescaling the unit (set new zero and span).