CHAPTER 3 - OPERATION

FLUID COMPONENTS INTL

Doc. No. 06EN003291 Rev. A

3 - 7

Model ST98 Flow Meter

Example:

Pressing [E] [ENTER] will always display “2.0 ma - 1k ohm”.

COMMAND:

F. K-Factor

Summary:

Permits the user to enter a K-Factor.

Description:

If the user determines that the flow rate output should be “biased”, a user supplied K-Factor can be applied to
modify the final flow reading from the calibrated flow rate.

Example:

Pressing [F] [ENTER] will display “K.F. = 1.0000000” on line 1 and "Change it?<" on line 2. Pressing [N]
[ENTER] will display "Input mode?<". Pressing [Y] [ENTER] will display "Enter K.F.#". Press in the new
K-Factor. Press [ENTER]. The new factor is saved and “Input mode ?<” is displayed.

COMMAND:

G. EEPROM

Summary:

For maintenance only. A passcode must be entered.

Description:

EEPROM byte locations can be read or modified.

Example:

N/A

COMMAND:

H. Heater

Summary:

Permits the user to toggle the heater circuit OFF and ON.

Description:

Useful whenever the heater needs to be turned off and on manually, i.e., while balancing the flow element or
trouble shooting the instrument.

Example:

Pressing [H] [ENTER] will display “Heater OFF!” or “Heater ON!” on line 1 depending on which state was
last active. “Input mode ?<” is displayed on line 2.