beautypg.com

Nutec, Fluid components international llc nutec, Series – Fluid Components International FS2000L User Manual

Page 6

background image

Fluid Components International LLC

NuTec

®

Series

This page is subject to the proprietary rights statement on the last page

6

Doc. No. 06EN003348 Rev. D

Input Power, Two Wire (Loop Power)

1. FCI recommends installing an input power disconnect and a 1/8 amp, fast blow fuse near the instrument to interrupt power during

installation, maintenance, calibration, alarm selection and troubleshooting procedures. Conduit should also be installed according to the

local electrical codes or hazardous location requirements. If the wires are to be pulled through the enclosure it is recommended that the

electronics be removed from the housing.

2. With the enclosure cover removed, slide the control circuit out half way to expose terminal block P1, Figure 13.
3. If the control circuit requires removal, slide out the control circuit and remove the green ground wire going to the ground screw. Discon-

nect the sensor element wires from the Ref and Act. Reinstall the control circuit before connecting the power and loads.

4. Connect the loop power leads to P1 as indicated on the control circuit. See Figure 11. Make sure that an earth ground wire is attached to

the earth ground terminal inside the housing. It is very important that the current loop connected to P1 maintains a voltage rang between

18 and 29.5 volts at the control circuit. Figure 11 shows a typical wiring configuration with a current sense device having 250&! imped-

ance. With this load, the power supply can be 22 to 33Vdc. Check the load impedance of the current sense device and the power supply

and see if they are compatible the NuTec instrument.

5. If the open collector switch is needed, make the connections to P1. See example circuit Figure 11.
6. After making all the wire connections, slide the control circuit into the housing until it passes the rim of the housing.
Refer to the next section for the set point and alarm state settings.

CURRENT

LOOP

TB 1

1.4K

EXAMPLE OF

AN OPEN

COLLECTOR

CIRCUIT

POWER

SUPPLY

OPEN

COLECTOR

+

+

-

-

+

-

250 ohm

4-20mA Current Loop

22 to 33

Vdc

18 to 29.5

Vdc

24Vdc

POWER

SUPPLY

+

-

Relay

C01067-1-1

AC

LINE

AC

NEUT

INPUT

RANG

E

10

0-2

40

V

A

C

50/60Hz

N/O

COM

N/C

6

AMPS

MAX

120/240

VAC

SN

OUTPUT A

N

D

RE
LA

Y

CONTROL

+

-

RELAY

TB4

FLUID COMPONENTS INTL

SAN MARCOS CA.

R

NuTec

T

M

TB5

TB6

TIE DOWN

BRACKET FOR

POWER WIRES

RELAY SHOWN

DE-ENERGIZED

OPEN C

GND

24 Vac

24 Vdc

TB 1

TOP

BOARD

(BOTTOM SIDE)

5 to 24

Vdc

ALARM

STATE

5 to 24 Vdc

5K

BOTTOM

BOARD

INPUT

POWER

RELAY

OUTPUT

EXAMPLE OF

AN OPEN

COLLECTOR

CIRCUIT

{

PRE-WIRED

}

PRE-WIRED

C01065-1-1

Figure 9 100 - 240 Vac Input Power

Figure 10 24 Vdc/Vac Input Power

Figure 11 2 Wire (LoopPower)

OPEN C

GND

24 Vac

24 Vdc

TB 1

BOTTOM SIDE

OF BOARD

5 to 24

Vdc

SUPPLY

ALARM

STATE

5 to 24 Vdc

5K

EXAMPLE OF

AN OPEN

COLLECTOR

CIRCUIT

24

Vac

24

Vdc

OR

COM

TB 2

N/C

N/O

RELAY

OUTPUT

RELAY SHOWN

DE-ENERGIZED

POWER

INPUT

-

+

C01066-1-1

This manual is related to the following products: