Doc. No. 06EN003250 Rev. N/C

2 - 3

FLT

Series FlexSwitch

Rack Mount

CHAPTER 2 - INSTALLATION

FLUID COMPONENTS INTL

Control Circuit Wiring

Mount the control circuit remotely by following the procedure below.

Warning:

Ensure that all power is OFF before wiring any circuit.

Wiring

The input/output connector for the control circuit is a 48 pin type F Eurocard connector, (DIN 41612). Shielded
cable must be used when running the cables to the sensing elements, as well as the signal voltage outputs if they are
used. Refer to Table 2-1 for the pin designations.

Table 2-1. Control Circuit Connector Pin-Outs

POWER SUPPLY PINS
P1-Z14

AGND

P1-D14

+24VDC

CH A RELAY PINS

ALARM 1

P1-D4

POLE

P1-B4

N.O.

P1-Z4

N.C.

ALARM 2

P1-D2

POLE

P1-B2

N.O.

P1-Z2

N.C.

CH A INPUT/OUTPUT PINS
P1-D12

OUT + A

P1-B12

OUT - A

P1-Z12

TEMP +A

P1-Z10

TEMP - A

P1-B14

SHIELD GND

P1-Z8

HTR + A

P1-B8

HRT RTN A

P1-D8

COM A

P1-D10

REF A

P1-B10

ACT A

P1-Z6

SHIELD GND

P1-D6

CHASSIS GND

CHANNEL A TEST CONNECTOR
P2-1

OUT +

P2-2

OUT -

P2-4

TEMP +

P2-8

TEMP -

P2-5

18V TEST POINT

P2-8

GND

CH B RELAY PINS

ALARM 1

P1-D32

POLE

P1-B32

N.O.

P1-Z32

N.C.

ALARM 2

P1-D30

POLE

P1-B30

N.O.

P1-Z30

N.C.

CH B INPUT/OUTPUT PINS
P1-D18

OUT + B

P1-B18

OUT - B

P1-Z18

TEMP +B

P1-Z16

TEMP - B

P1-B16

SHIELD GND

P1-Z22

HTR + B

P1-B22

HRT RTN B

P1-D22

COM B

P1-D20

REF B

P1-B20

ACT B

P1-Z20

SHIELD GND

P1-D28

CHASSIS GND

CHANNEL B TEST CONNECTOR
P2-6

OUT +

P2-7

OUT -

P2-9

TEMP +

P2-8

TEMP -

P2-10

18V TEST POINT

P2-8

GND

Remote Mounting

1.

Mount the control circuit rack to an appropriate and accessible surface. (See Figure 2-1.)

2.

FCI's recommendation is to install conduit between the local enclosure and the remote enclosure, as well as
installing conduit between the remote enclosure and the power source and monitoring circuit. Provide water
tight hardware and apply thread sealant to all connections to prevent water damage.