Burkert Type 8631 User Manual
Page 2

The control head must not be exposed directly to
sunshine or strong light sources: this would cause
additional warming!
Connections:
2 x M16 cable connector with screw terminals
for cable cross-sections 0,14 ... 1,5 mm²
Power supply:
Sensor
see Manufacturer's Declaration form
Fa. Pepperl & Fuchs
1)
Valve
see Qualification Test Certificate
PTB 01 ATEX 2173
1)
1)
see detailed operating instructions
DEVICES WITH EEx-i-APPROVAL
DEVICES WITH EEx-i-APPROVAL
The maximum permissible voltages and the associated
maximum permissible short-circuit currents for the
corresponding gas group may be taken from Table A1 in the
standard DIN EN 50020, 1994 Edition.
In order that the maximum permissible temperature at the
solenoid coil of the valve installed is not exceeded, the following
limits to the applied power for use in the corresponding
temperature class must be observed:
Please comply with the following:
• In the case of installation and operation in areas that have a
risk of explosion, the respective national regulations. In
Germany, this is VDE 0165.
• When making electrical connections to the inherently safe
circuit, the information given in the corresponding conformity
certificates.
• Always follow the information contained in the ATEX approval.
Operating conditions
Ambient temperature
-10... +50°C
Protection class
IP 65 nach EN 60529
Electrical data
Voltage supply
(see nameplate)
24 V DC ± 10 %
3)
110 / 230 V AC
4)
Protection class
3 to VDE 0580
Pneumatic data
Control medium
Quality classes
to DIN ISO 8573-1
- Dust content
max. particle size 40
max. particle density
- Water content
max. pressure dew po
- Oil content
max. 25 mg/m
3
Temperature range of
compressed air
-10 ... +50 °C
Pressure range
3 ... 7 bar
observe the notes in these operating
ons together with the conditions of use and
hat are specified in the data sheet Type 8631, in
evice will function perfectly and remain operable
On non-observance of these notes and
erference with the device, we will refuse all
warranty on device and accessories will become
serves exclusively to actuate pneumatically
s valves. Any other use or use exceeding the
considered to be
non-intended use. Bürkert
for any damage resulting therefrom. The risk will
user.
e
ains electronic components that are sensitive to
harge (ESD). Contact to electrostatically charged
ts will endanger these components. In the worst
e immediately destroyed or will fail after
Observe the requirements of EN 100 015 - 1 in
e the possibility of, or avoid, damage from
ectrostatic discharge. Also take care not to touch
are under supply voltage.
ATTENTION
EXERCISE CAUTION ON HANDLING!
ELECTROSTATICALLY SENSITIVE
COMPONENTS / MODULES
Notes for use in the Ex-area
When connecting units with EEx-i approval, always
follow the operation instructions in detail!
Notes for devices with EEx-i-approval
OTES
DEVICES WITH EEx-i-APPROVAL
Electrical data (EEx-i-approval)
TECHNICAL DATA
Temperature
class
Max. permissible ambient
temperature
2)
[°C]
Max. permissible
power [W]
T6
+50
0,4
+45
0,5
+40
0,7
+35
0,8
T5
+50
0,8
+45
1,0
+40
1,1
2)
Ambient temperature for compl. TopControl 8631
(temperature inside the device is higher by max. 5°C )
Functional data
Resistance at 20°C (R
20
):
510 Ohm
Minimum terminal voltage:
11,7 V
Minimum current:
23 mA
The maximum voltage and current values are determined by the
permissible electrical operating equipment.
Technical Data
3)
Attention: do not use insustrial DC.
4)
At present not available
We reserve the right to make technical changes without
• Take suitable measures to avoid an electrostatic discharge
from the plastic parts of the housing (see EN 100 015 - 1).
• No component should be connected to the inputs and
outputs of the circuit board whose electrical data is outside
the limits determined for intrinsically safe operation quoted in
the data sheet of the positioner.
• Work out on the device with the housing open should not be
carried in very damp or aggressive atmospheres. Take
precautions to exclude unintentional mechanical damage to
the circuit boards or their components. Limit the period during
which the unit is opened to that which is absolutely
necessary.
Safety requirements