24
Serial Communication
command number
command name
Device types
0x98
extSetpointWithoutanswer
0xee
request
Command
0x92
Byte count
5
data
1 byte
0
Set-point value settings, internal
1
Set-point value settings, external
4 bytes
1 ... 4
Set-point value [%] (float)
9)
response
Command
-
Byte count
-
Status
-
data
-
Description
determines the set-point value settings and describes the external set-point value as a percentage:
Internal = analog - the set-point value settings is assigned by the analog
set-point value signal that is created
External = RS232, RS485
No response is sent for this command.
Command 0x98 - ExtSetpointWithoutAnswer
Table 14:
First byte transferred: MSB
9)
english
Typ 8605
See also other documents in the category Burkert Accessories for water:
- Type 0125 (15 pages)
- Type 0121 (4 pages)
- Type 0330 (2 pages)
- Type 0331 (4 pages)
- Type 6012 (4 pages)
- Type 0127 (18 pages)
- Type 0131 (5 pages)
- Type 0141 (5 pages)
- Type 0142 (12 pages)
- Type 0145 (3 pages)
- Type 0174 (5 pages)
- Type 0212 (2 pages)
- Type 0211 (5 pages)
- Type 0212-B (18 pages)
- Type 0250 (64 pages)
- Type 0253 (2 pages)
- Type 0255 (15 pages)
- Type 0355 (2 pages)
- Type 0255 (2 pages)
- Type 8006 (34 pages)
- Type 8640 (2 pages)
- Type 8640 (55 pages)
- Type 8640 (119 pages)
- Type 0256 (15 pages)
- Type 0256 (2 pages)
- Type 0258 (72 pages)
- Type 0262 (5 pages)
- Type 0273 (6 pages)
- Type 0280 (5 pages)
- Type 0280 (2 pages)
- Type 0280 (12 pages)
- Type 0281 (2 pages)
- Type 0282 (2 pages)
- Type 0283 (2 pages)
- Type 0286 (4 pages)
- Type 0287 (15 pages)
- Type 0290 (2 pages)
- Type 0290 (14 pages)
- Type 0293 (18 pages)
- Type 0300 (6 pages)
- Type 0301 (6 pages)
- Type 0311 (2 pages)
- Type 0312 (6 pages)
- Type 6518 (57 pages)
- Type 6519 (3 pages)