Burkert Type 8605 User Manual
Page 13

13
Serial Communication
long frame address (5 bytes)
Bit 0 (MSB)
Master Address (m)
0: Secondary Master
1: Primary Master
Bit 1
Burst Info (b)
0: Not in burst mode
1: In burst mode
Bit 2 ... 7
Manufacturer Id Code (x) (Bit 2 = MSB, Bit 7 = LSB)
0x78
hex
= Burkert
Bit 8 ... 15
device Type Code (y) (Bit 8 = MSB, Bit 15 = LSB)
0xEB
hex
= 8605
Bit 16 ... 39 (LBS)
device Id Number (z) (Bit 16 = MSB, Bit 39 = LSB),
(corresponds to the address, results from an XOR link between identification number and
serial number of the device)
Each field device must reply to address 0 (bit 2 … 39 = 0) (broadcast telegram)
Byte 4
mbxxxxxx
Byte 4
yyyyyyyy
Byte 4
zzzzzzzz
Byte 4
zzzzzzzz
Byte 4
zzzzzzzz
z: device Id Number
y: device Type Code
x: Manufacturer Id Code
b: Burst Info
m: Master Address
Long Frame Adresse
Fig. 7:
command
3.4.5.
Commands are divided into the following categories in conformity with HART:
Universal commands
Commands 0 ... 30
Standard commands
Commands 32 ... 126 (123 ... 126 not public)
device-specific command
Commands 128 ... 253
(reserved: 31, 127, 254, 255)
Byte count
3.4.6.
The byte count indicates how many more bytes come before the checksum, i.e. the number of status bytes +
number of data bytes. This results in a maximum total number of 255 status and data bytes.
english
Typ 8605