beautypg.com

Burkert Type 8605 User Manual

Page 13

background image

13

Serial Communication

long frame address (5 bytes)
Bit 0 (MSB)

Master Address (m)
0: Secondary Master
1: Primary Master

Bit 1

Burst Info (b)
0: Not in burst mode
1: In burst mode

Bit 2 ... 7

Manufacturer Id Code (x) (Bit 2 = MSB, Bit 7 = LSB)
0x78

hex

= Burkert

Bit 8 ... 15

device Type Code (y) (Bit 8 = MSB, Bit 15 = LSB)
0xEB

hex

= 8605

Bit 16 ... 39 (LBS)

device Id Number (z) (Bit 16 = MSB, Bit 39 = LSB),
(corresponds to the address, results from an XOR link between identification number and
serial number of the device)
Each field device must reply to address 0 (bit 2 … 39 = 0) (broadcast telegram)

Byte 4
mbxxxxxx

Byte 4
yyyyyyyy

Byte 4
zzzzzzzz

Byte 4
zzzzzzzz

Byte 4
zzzzzzzz

z: device Id Number
y: device Type Code
x: Manufacturer Id Code
b: Burst Info
m: Master Address

Long Frame Adresse

Fig. 7:

command

3.4.5.

Commands are divided into the following categories in conformity with HART:
Universal commands

Commands 0 ... 30

Standard commands

Commands 32 ... 126 (123 ... 126 not public)

device-specific command

Commands 128 ... 253
(reserved: 31, 127, 254, 255)

Byte count

3.4.6.

The byte count indicates how many more bytes come before the checksum, i.e. the number of status bytes +
number of data bytes. This results in a maximum total number of 255 status and data bytes.

english

Typ 8605