6510/6511 - 15

INSTALLATION, INITIALISATION AND SERVICE

english

Faults

Fault

Possible cause

Correction

Valve does not
switch:

Operational voltage too low or

not present;

Check the electrical supply connections.

Ensure that the electrical power supply is the same as

that specified on the rating plate.

Manual override not in neutral
position;

Set the manual override to the zero position.

Compressed air supply

Carry out the dimensioning of the compressed air
connection with volumes as large as possible (including

that of upstream pressure regulators, service units, cut-
off valves etc.)

Minimum operational pressure

≥ 2,5 bar

Valves switch
with a delay, or
exhaust
through the
venting ports

Compressed air supply not
available or insufficient;

Carry out the dimensioning of the compressed air
connection with volumes as large as possible (including
that of upstream pressure regulators, service units, cut-
off valves etc.).

Minimum operational pressure

≥ 2,5 bar

Valves are not in the starting

position (without current)
during pressure build-up

Apply pressure to the valve block before you switch the
valves.

Insufficient venting of the

exhaust channels due to
silencers that are too small or
are soiled (back-pressure);

Use silencers or expansion channels with sufficient

dimensions. Clean soiled silencers.

Impurities or foreign matter in

the pilot valve or main valve

Blast through the exhaust channels with polsed

compressed air, to blow out impurities. Install a new pilot
or main valve if these measures bring no improvement.

Leaking valve
block

O-rings between the modules

missing or damaged;

Check for leaks and for missing seals

Missing or incorrectly
positioned flat seals between

the valve and teh baseplate

Install the missing seals and replace damaged seals