INSTALLATION, INITIALISATION AND SERVICE
english
Faults
Fault
Possible cause
Correction
Valve does not
switch:
Operational voltage too low or
not present;
Check the electrical supply connections.
Ensure that the electrical power supply is the same as
that specified on the rating plate.
Manual override not in neutral
position;
Set the manual override to the zero position.
Compressed air supply
Carry out the dimensioning of the compressed air
connection with volumes as large as possible (including
that of upstream pressure regulators, service units, cut-
off valves etc.)
Minimum operational pressure
≥ 2,5 bar
Valves switch
with a delay, or
exhaust
through the
venting ports
Compressed air supply not
available or insufficient;
Carry out the dimensioning of the compressed air
connection with volumes as large as possible (including
that of upstream pressure regulators, service units, cut-
off valves etc.).
Minimum operational pressure
≥ 2,5 bar
Valves are not in the starting
position (without current)
during pressure build-up
Apply pressure to the valve block before you switch the
valves.
Insufficient venting of the
exhaust channels due to
silencers that are too small or
are soiled (back-pressure);
Use silencers or expansion channels with sufficient
dimensions. Clean soiled silencers.
Impurities or foreign matter in
the pilot valve or main valve
Blast through the exhaust channels with polsed
compressed air, to blow out impurities. Install a new pilot
or main valve if these measures bring no improvement.
Leaking valve
block
O-rings between the modules
missing or damaged;
Check for leaks and for missing seals
Missing or incorrectly
positioned flat seals between
the valve and teh baseplate
Install the missing seals and replace damaged seals