General information, Application conditions of the devices, Short-circuit protection – Burkert Type 6013 User Manual
Page 7

7
General information
4.
GENERAL INFORMATION
4.1.
Contact addresses
Germany
Bürkert Fluid Control Systems
Sales Center
Christian-Bürkert-Str. 13-17
D-74653 Ingelfingen
Tel. + 49 (0) 7940 - 10 91 111
Fax + 49 (0) 7940 - 10 91 448
E-mail: [email protected]
International
Contact addresses can be found on the final pages of the printed
operating instructions.
And also on the Internet at:
4.2.
Warranty
The warranty is only valid if the device is used as intended in accordance
with the specified application conditions.
4.3.
Information on the Internet
The operating instructions and data sheets for Type 6013 can be found
on the Internet at:
5.
APPLICATION CONDITIONS OF
THE DEVICES
5.1.
Short-circuit protection
To protect against short-circuits, either a fuse (max. 3 x I
b
in accordance
with IEC 60127-2-1) must be connected upstream of each magnet
according to the rated current of the magnet, or a motor protection
switch with short-circuit and thermal quick release (set to rated current).
If rated currents of the magnet are very low, the fuse with the lowest
current value is adequate in accordance with the stated IEC standard.
This fuse may be housed in the associated supply unit or must be
connected separately upstream. The rated voltage of the fuse must be
equal to or greater than the indicated nominal voltage of the magnet.
The breaking capacity of the fuse insert must be equal to or greater
than the maximum short-circuit current accepted at the installation
location (usually 1500 A).
Fuse
0,08 A
The nominal fuse value is indicated
on the magnet.
english
PTB 00 ATEX 2129 X