Assembly

Type 2000 INOX

6. ASSEMBLY

DANGER!

Risk of injury from high pressure in the system!
• Turn off the pressure and vent the lines before loosening lines

or valves.

WARNING!

Risk of injury from improper assembly!
• Installation must only be carried out by authorized technicians

and with the appropriate tools!

Risk of injury from unintentional activation of the system and
uncontrolled restart!
• Secure system from unintentional activation.
• Following assembly, ensure a controlled restart.
Risk of crushing from moving pneumatic connection!
• When opening and closing the device, do not touch the moving

pneumatic connection.

• Do not reach into the area immediately above and below the

control air connection.

6.1. Preparatory work

Before connecting the valve, ensure the pipelines are flush
(stress-free).

Clean pipelines (sealing material, swarf, etc.).

Devices with welded body:
Remove the actuator from the valve body:

Clamp the valve body into a holding fixture.

NOTE!

Damage to the seat seal or the seat contour!

Open the valve for control functions A: Pressurize the lower
pilot air port with compressed air (5 bar).

Place a suitable open-end wrench on the wrench flat of the nipple.

Unscrew the actuator off the valve body.

Devices with threaded body:

Only disassemble the actuator if required by the customer.

6.2. Installation

6.2.1. Installing valve housing in pipeline

For welded housings:

Weld valve housing in pipeline system.

Check graphite seal and, if required, replace.

Graphite seal

For other housing models:

Connect valve housing to pipeline.