Inspection, Warning – ClimaCool IOM FLEX SERIES User Manual
Page 4

www.climacoolcorp.com
www.climacoolcorp.com
®
2
INSPECTION
Allow a sufficient amount of time to carefully follow these 
instructions to assure warranty coverage.
During inspection of the equipment remove the top doors 
to check the equipment for any damage during shipment. 
Inspect wiring connections, lines from expansion devices, 
thermostats, and pressure switches for damage.
General
During any correspondence concerning this machine, always 
reference the full model and serial numbers of your modules. 
Receipt of the ClimaCool Modules
Upon receipt of the equipment, carefully check the shipment 
against the bill of lading. Make sure all modules ordered have 
been received. Inspect the carton or crating of each module, 
and inspect each module for damage. You must make 
proper notation of any shortages or damage on all copies 
of the freight bill for your records. Make sure the carrier 
completes a common carrier inspection report listing any 
shortages or damage. 
Note: It is the responsibility of the recipient of the 
modules to file all necessary claims with the carrier. In 
addition, please notify the ClimaCool Customer Service 
Department of all damage immediately. Refer to the 
back cover for the Customer Service Department phone 
number.
Storage
Equipment should be stored as shipped in a clean, dry area. 
Store modules in an upright position at all times. Plastic wrap 
should be left on until the module is ready to be installed.
Handling of Modules
The packaging allows for handling by fork lift or pallet 
jack (only lift the module from the side). See Lifting and 
Transporting Modules (Fig. 3) on page 5. 
Caution: modules
ARE TOP HEAVY. Please use caution when rigging or 
moving. 
Rigging for Lifting
Each module should be lifted by using lift straps threaded 
through each top header tube. See page 5 - Rigging and 
Lifting Procedures.
�
WARNING
�
To avoid the release of refrigerant into the atmosphere, 
the refrigerant circuit of this unit must be serviced only by 
technicians who meet local, state and federal proficiency 
requirements.
All refrigerant discharged from this unit must be recovered 
WITHOUT EXCEPTION. Technicians must follow industry 
accepted guidelines and all local, state and federal statutes for 
the recovery and disposal of refrigerants.
If a compressor is removed from this unit, system refrigerant 
circuit oil will remain in the compressor. To avoid leakage of 
compressor oil, the refrigerant lines of the compressor must 
be sealed after it is removed.
Inspection
