Automatic Timer Flush ATF-EA-1.5 (optional)

Valve Specifications

A.

Water-resistant Polypropylene Motor Case

B.

High Torque Motors with Perma-lube Gears

C.

Open & Close Indicator

D.

Stainless Steel Ball Valve & Hardware

E.

Auto Reset Circuit Breaker

F.

90 Degree Bidirectional Rotation

G.

Controller Case

Fig. 3

Automatic Timer Flush Package Option

TROUBLESHOOTING: If you require further assistance, please call us at (405) 745-3185.

PROBLEM

POSSIBLE CAUSE

SOLUTION

• Valve is leaking past ball

• Seals damaged or worn out

• Install repair kit

• Valve is not stopping at proper

• Adjust limit switches

closed position

• Valve stem leaks

• Worn stem seals

• On metal valves: tighten stem packing

nut 1/2 turn.

CAUTION! Over tightening stem nut
could cause drag on motor and trip
internal circuit breaker. May require
repair kit or new valve.

• Valve body leaks

• Loose body bolts or excessive operating

• Check bolts and observe recommended

pressure

ratings

• Defective seals

• Install repair kits or new valve

• Valve hard to turn

• Swollen seals or product buildup in valve

• Check valve for compatibility with

chamber

product, may require valve cleaning or

new valve

• Valve bolts too tight

• Loosen bolts slightly

• Stem nut too tight

• Loosen stem nut slightly