21

Description:
The pressure differential alarm option continually monitors
and displays the strainer’s inlet and outlet differential
pressure. When the strainer element (conical strainer basket)
becomes significantly clogged, the pressure differential
switch-gauge will trigger an audible siren and a visual
flashing alarm light. These alarms are intended to alert
maintenance personnel that the strainer element must be
removed and cleaned (see page 18 for complete strainer
element cleaning instructions).

Operation Instructions:
Remove the power supply and insert the connector end into
the socket on the bottom of the PDA housing, as indicated
in the drawing above. Plug the transformer into the power
source. Standard systems are supplied with a 120V power
supply to the primary of the transformer, with an output,
secondary of 12 VDC.

The pressure differential switch-gauge is factory set to
7-8 PSI. The ClimaCool Strainer operates at a pressure
differential slightly less than 1 PSI during maximum flow
when the strainer screen is clean. By the time this differential
pressure reaches 7-8 PSI, the strainer element will be
significantly clogged and require immediate removal and
cleaning.

To adjust the pressure differential switch-gauge setting, insert
a 1/16” allen wrench and rotate the differential set-point
contact to the desired location (see Fig. 1).

Note: We do not recommend setting the differential
switch-gauge higher than 10 PSI. Disabling the alarm
or increasing the alarm set point could result in damage
to the strainer element and allow debris to pass into the
system.

Pressure Differential Alarm Option

PSID High

PSID Low

Pressure Differential Alarm (PDA) option

Alarm Reset Button

FRONT

VIEW

LEFT SIDE

VIEW

Power To ATF

110 Volt/12 Volt DC

Wall Transformer

Visual

Alarm

Audible

Alarm

Pressure Differential

Switch-Gauge

LED Power Indicator

Differential

Set-Point Contact

Cover-Plate Screw (4) in Corners of

Box (DO NOT REMOVE).

Visual

Alarm

RIGHT SIDE

VIEW

TOP

VIEW

BOTTOM

VIEW

AUX Contacts

(On or Off with Alarm)

Red & Black

Cable Retainer