Pre start up check list, Pre start-up check list* (water-cooled) – ClimaCool IOM FLEX SERIES User Manual
Page 28
www.climacoolcorp.com
www.climacoolcorp.com
®
26
Pre Start Up Check List
PreStartUp WaterCool Rev. 0508
Project Name: _________________________ Date: ___________________
Address: _________________________
_________________________
YES NO
1
.
Are modules connected properly “per Codes and Installation Manual”?
____ ___
(Installation, Operation & Maintenance Manual is available at
www.climacoolcorp.com
)
2
.
Is there a 60-80 mesh strainer on condenser & evaporator inlet water?
____ ___
(Fill water to Chiller through upstream 60-80 mesh strainer.)
3.
Is Condenser water system filled & flushed?
____ ___
(See “Filling the Water System” in ClimaCool IO&M.)
4.
Is Chilled water system filled, flushed & all air purged from system?
____ ___
(All air must be purged from system prior to startup. See “Filling the Water System” in ClimaCool IO&M.)
5.
Are all pumps tested & operational?
____ ___
6.
Are required GPM’s being provided to Chiller?
____ ___
(See project selection and performance sheets available from ClimaCool Sales Rep.)
7.
Is required Differential Pressure being provided to Chiller?
____ ___
(See project selection and performance sheets available from ClimaCool Sales Rep.)
8.
Flow & differential switches set to trip on drop below required flows?
____ ___
(Set to trip on low flow (less than 75% flow), not pump on/off.)
9
.
Have all Chiller flange connections been leak tested?
____ ___
10.
Is there water presently circulating through chiller?
____ ___
11
.
Is power and control wiring complete to each module?
____ ___
(Note: All Chiller covers are removable DO NOT Attach Wiring Etc.)
12
.
Do wiring & devices meet with approved control submittal drawings?
____ ___
13
.
Is required load available to run multiple compressors at start-up?
____ ___
14
.
Is control functional to maintain condenser water temperature?
____ ___
(This includes maintaining “minimum” inlet temperature. See “Operational Limitations” in ClimaCool IO&M.)
15
. Are water quality parameters tested and in compliance with ClimaCool IO&M?
(See “Water Treatment” in ClimaCool IO&M for required Water Quality Parameters.)
If you checked “No” to any question above, provide the line reference number and the date of scheduled completion below.
Please note, all conditions must be complete prior to the start-up date.
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
*This form must be completed and submitted to ClimaCool Corp.a minimum of two (2) weeks prior to final scheduling of
any Start-up.
Note: If any of the above items are not complete at time of start-up, backcharges will be assessed for additional costs.
Contractor Name: ___________________________ __________________________________
Address: ___________________________
(Authorized Signature)
___________________________
Phone: ___________________________ Date: _____________________________
Pre Start-Up Check List*
(Water-Cooled)
or Fax 405-745-2072
T H E U L T I M A T E C H I L L E R S O L U T I O N
®
®