Run
Compressor
for 5 Minutes
Is Superheat
in Range?
Yes
No
Is Subcooling
in Range?
Yes
No
Is Superheat
Low or High?
High
Low
Turn TXV
Adjustment
Stem Clockwise
Is Subcooling
Low or High?
High
Low
Add Refrigerant
Is Subcooling
Low or High?
High
Low
Recheck Superheat
and Complete
Start-up and
Warranty Form
Add Refrigerant
Remove
Refrigerant
Turn TXV
Adjustment Stem
Counter Clockwise
Water Testing
Extract three water samples from each water loop, Hot Water/Condenser, Chilled Water/Evaporator using the bottles
provided (three (3) bags; each bag containing three (3) bottles) from the Water Sample test kit. Confirm that the
sample bottles are filled to the top leaving no air in the bottles. All the sample bottles must have labels completed per
instructions included with the bottles. Ship the bottles immediately to the appropriate water testing laboratory per
the instructions.
Startup Documentation
All startup paperwork and documentation must be submitted to ClimaCool . Future warranty claims cannot be processed
without a completed Startup and Warranty Registration form on file (See page 27-29).
Note: Electronic version of the Startup forms available on www .climacoolcorp .com in the Library section .
Caution: Do not charge to achieve subcooling temperature when the expansion valve is overfeeding. If the expansion
valve is overfeeding, readings may still indicate low subcooling and low superheat, but circuit may not be undercharged.
Subcooling & Superheat