Dialight D1RW-B13-008 SafeSite L-864/L-865 Flashing Dual LED Class I Div. 2 (White/Red) Strobe User Manual
Page 8

Document No.
9100-127-1383-99 Rev B
Release Date: 10/7/2010
_____________________________________________________________________
_____________________________________________________________________________
Dialight Corporation 1501 Route 34 South Farmingdale NJ 07727
Tel: 732.919.3119 Fax: 732.751.5778 Web: www.dialight.com
Page 8 of 25
Section 4: System Installation Recommendations for EMC and Lightning
Immunity
1: Electrically bond the shield of the Flash Head cable to ground at both ends.
Make 360-degree ground connections around the braid or foil (avoid pigtails).
2: If there is a drain-wire in the cable, connect to ground at both ends
3: Ensure the Flash Head is electrically bonded to the tower
4: Minimize loop areas by tying all cables against the tower or passing through
conduit
5: Ensure the power-supply cabinet is electrically bonded to the tower
6: Ground any spare/unused conductors in the Flash Head cable at both ends
7: Keep wiring tidy with cables performing different functions tied up separately.
Keep power, control and output cables separate. Tie up wires to minimize loop
areas.
For a detailed step by step procedure, refer to “Recommendations for
Proper Grounding to Minimize Lightning Damage” guide available at
http://www.dialight.com/assets/installation_manuals/9100127140699.pdf