Important Information:

These instructions contain important safety information, read and follow them carefully. Dialight will not accept any

responsibility for injury, damage or loss which may occur due to incorrect installation, operation or maintenance.

Safety Instructions:


The installation, operation and maintenance must be
carried out by an electrician suitably trained in
hazardous areas and with knowledge of increased
safety explosion protection IEC 60079-14

The technical data indicated on the LED fixture are
to be observed.

Changes of the design and modifications to the
LED fixture are not permitted.


Repairs must only be carried out by a qualified
electrician with hazardous area knowledge.

Only genuine Dialight Europe Ltd replacement
parts must be used when unforeseen repairs are
required.


Observe the national safety rules and regulations
during installation.

Do not keep these operating instructions inside the
LED fixture during operation.

Do not open the LED fixture when energised.

Wait 10 minutes before opening after de-energising
the LED fixture.


Technical Data


Category of application

Ex d e mb IIC T6 Gb
Ex tb IIIC T85°C Db
IP66/67

II 2GD


IECEx

IECEx BAS 10.0051X

ATEX

Baseefa10ATEX0092X

Rated Input Voltage:

100-277VAC 50/60Hz


Rated Input Current:

200mA at 100V / 100mA
at 230V Typical


Housing Material:

LM6 Copper free Alu.


Housing Colour:

RAL 7001 / RAL 7011

RAL 8011 / RAL 9005

RAL 8019


Storage Temp.

-60°C to +60°C

original packaging:


Dimensions:

see Figure.1


Protection Glass:

Toughened Glass
Frosted or Clear.


Cable Entries:

2 OFF M20 x 1.5mm


Tightening Torques

See Table


Weight:

4.75kg (10.50 lbs)

A80-000553 Issue A