Atec Chroma-62000H Series User Manual
Page 8
![background image](/manuals/318423/8/background.png)
Distributed by:
JAPAN
CHROMA JAPAN CORP.
11F NARA Building II 2-2-8
Shinyokohama, Kouhokuku,
Yokohama City 222-0033
Kanagawa, Japan
Tel: +81-45-470-2285
Fax: +81-45-470-2287
http://www.chroma.co.jp
U.S.A.
CHROMA SYSTEMS
SOLUTIONS, INC.
25612 Commercentre Drive,
Lake Forest, CA
92630-8830
Tel: +1-949-600-6400
Fax: +1-949-600-6401
Toll Free: +1-866-600-6050
http://www.chromausa.com
E-mail: [email protected]
Developed and Manufactured by :
CHROMA ATE INC.
致茂電子股份有限公司
HEADQUARTERS
No. 66, Hwa-Ya 1st Rd.,
Hwa-Ya Technology Park,
Kuei-Shan Hsiang,33383
Taoyuan County 33383
Taiwan
Tel: +886-3-327-9999
Fax: +886-3-327-8898
http://www.chromaate.com
E-mail: [email protected]
EUROPE
CHROMA ATE EUROPE B.V.
Morsestraat 32, 6716 AH Ede,
The Netherlands
Tel: +31-318-648282
Fax: +31-318-648288
http://www.chromaeu.com
E-mail: [email protected]
CHINA
CHROMA ELECTRONICS
(SHENZHEN) CO., LTD.
8F, No.4, Nanyou Tian An
Industrial Estate, Shenzhen,
China PC: 518052
Tel: +86-755-2664-4598
Fax: +86-755-2641-9620
Worldwide Distribution and Service Network
62000H-201008-2000
MODEL
62100H-600S*1
62150H-600S
62150H-1000S*1
Output Ratings
Output Voltage
0-600V
0-600V
0-1000V
Output Current
0-17A
0-25A
0-15A
Output Power
10000W
15000W
15000W
Line Regulation
Voltage
+/- 0.01% F.S.
Current
+/- 0.05% F.S.
Load Regulation
Voltage
+/- 0.05% F.S.
Current
+/- 0.1% F.S.
Voltage Measurement
Range
120V / 600V
120V / 600V
200V / 1000V
Accuracy
0.05% + 0.05%F.S.
Current Measurement
Range
6.8A / 17A
10A / 25A
6A / 15A
Accuracy
0.1% + 0.1%F.S.
Output Noise&Ripple
Voltage Noise(P-P)
1500 mV
1500 mV
2550 mV
Voltage Ripple(rms)
650 mV
650 mV
1950 mV
Current Ripple(rms)
300 mA
450 mA
90mA
OVP Adjustment Range
Range
0-110% programmable from front panel, remote digital inputs.
Accuracy
+/- 1% of full-scale output
Programming Response Time
Rise Time: 50%F.S. CC Load
30ms
30ms
25ms
Rise Time: No Load
30ms
30ms
25ms
Fall Time: 50%F.S. CC Load
30ms
30ms
25ms
Fall Time: 10%F.S. CC Load
100ms
100ms
80ms
Fall Time: No Load
1.2s
1.2s
3s
Slew Rate Control
Voltage Slew Rate Range
0.001V/ms - 20V/ms
0.001V/ms - 20V/ms
0.001V/ms - 40V/ms
Current Slew Rate Range
0.001A/ms - 0.1A/ms, or INF
0.001A/ms - 0.1A/ms, or INF
0.001A/ms - 0.1A/ms, or INF
Minimum Transition Time
0.5ms
Transient response time
Recovers within 1ms to +/- 0.75% of steady-state output for a 50% to 100% or 100% to 50% load change(1A/us)
Efficiency
0.87(Typical)
Programming & Measurement Resolution
Voltage (Front Panel)
10 mV
10 mV
100mV
Current (Front Panel)
1mA
1mA
1mA
Voltage (Digital Interface)
0.002% of Vmax
Current (Digital Interface)
0.002% of Imax
Voltage (Analog Interface)
0.04% of Vmax
Current (Analog Inteface)
0.04% of Imax
Programming Accuracy
Voltage (Front Panel and Digital Interface)
0.1% of Vmax
Current (Front Panel and Digital Interface)
0.3% of Imax
Voltage (Analog Interface)
0.2% of Vmax
Current (Analog Interface)
0.3% of Imax
Series & Parallel Operation*2
Master / Slave control via CAN for 10 units up to 150KW. (Series: two units / Parallel: ten units )
Auto Sequencing(I-V program)
Number of program
10
Number of sequence
100
Dwell time Range
1s - 15,000S
Trig. Source
Manual / Auto
General Specification
Maximum Remote Sense Line Drop Compensation
2% of full scale voltage per line (4% total)
Operating Temperature Range
0
0
C ~ 40
0
C
Storage Temperature Range
-40
0
C ~ +85
0
C
Dimension (HxWxD)
132.8 mm x 428 mm x 610 mm / 5.23 x 16.85 x 24.02 inch
Weight
Approx. 29 kg / 63.88 lbs
Approx. 35 kg / 77.09 lbs
Approx. 35 kg / 77.09 lbs
Approval
CE
CE
CE(Optional)*
1
ElEctrical SPEciFicatiONS - Solar array Simulator Model
Note*1 :
Call for Availability.
Note*2 :
To parallel operation more than 5 units, please contact factory. There is parallel mode for DC power supply when the I-V curve function is enabled.
All specification are subject to change without notice.