0 specifi cations – Alpha Technologies VMX Series User Manual
Page 54
54
017-940-B0-001, Rev. A
7.0 Specifi cations
Model:
VMX 615CE
VMX 622CE-48
VMX 915E
Electrical
Input Voltage:
230Vrms
230Vrms
230Vrms
Input Tolerance:
Operating: ±158 to 292Vrms
Operating: ±158 to 292Vrms
Operating: ±158 to 292Vrms
Line Return: ±169 to 281Vrms
Line Return: ±169 to 281Vrms
Line Return: ±169 to 281Vrms
Nominal Input Current
1
:
5A
7A
7A
Input Frequency:
50Hz, ±3Hz
50Hz, ±3Hz
50Hz, ±3Hz
DC Voltage:
36VDC
48VDC
36VDC
Low DC Voltage Cutout:
1.75V/Cell
1.75V/Cell
1.75V/Cell
Output Voltage:
63V rms
48/63V rms (Field Selectable)
63/87V rms (Field Selectable)
Output Regulation, High TAP
2
:
±3%
±3%
±3%
Output Regulation, Low TAP
2
:
±4%
±4%
±4%
Rated Output Current:
15A rms
22A rms
15A rms
Output Confi guration:
4 Programmable Outputs
4 Programmable Outputs
4 Programmable Outputs
Output Frequency:
50Hz, ±1Hz (Inverter Operation)
50Hz, ±1Hz (Inverter Operation)
50Hz, ±1Hz (Inverter Operation)
Waveform:
Quasi Square wave
Quasi Square wave
Quasi Square wave
Slew Rate:
<200 V/ms, <100 V/ms typical
<200V/ms, <100V/ms typical
<200V/ms, <100V/ms typical
Crest Factor Ratio (Peak: RMS):
1.3:1 typical
1.3:1 typical
1.3:1 typical
Auxiliary Output 150W rated UPS:
205-260V (line), 170-265V (Inv)
205-260V (line), 170-265V (Inv)
205-260V (line), 170-265V (Inv)
Effi ciency @ Default TAP Settings
@100% Load:
91% typical at nominal input
@75% Load:
90% typical at nominal input
@50% Load:
88% typical at nominal input
@25% Load:
80% typical at nominal input
On Inverter (40 to 100% load):
80% typical
Overload Protection
Fold back (Typical @ Nominal Input)
87V
TAP:
N/A N/A 24A
rms
63V TAP:
33A rms
35A rms
33A rms
48V TAP:
N/A
45A rms
N/A
Output Current Into Short (@ Nominal Input)
87V TAP:
N/A
N/A
<22.5A rms
63V TAP:
29A rms typical
<30A rms
29A rms typical
48V TAP:
N/A
<33A rms
N/A
Overload Current Operation
0% to 110% Load:
Continuous Operation
110 to 115% Load:
Continuous Operation with Alarm
115 to 125% Load:
Shut Down approx. 30min
125 to 150% Load:
Shut Down approx. 10min
>150% Load:
Shut Down <10sec
Battery Charging
Charge Current
3
:
10A
Temperature Compensation
:
-5mV/Cell/°C (Programmable)
Constant Current Operation:
High Rate Charge to 90% Capacity
Constant Voltage Operation:
2.40V/Cell (Programmable)
Environmental
Operating Range:
–40 to 55°C at Front Air Inlet of Power Supply
Humidity:
0 to 95% non-condensing
Altitude:
0 to 10000ft (3000m) above sea level
Mechanical
Vertical Mount
Shelf Mount
Vertical Mount
Shelf Mount
Vertical Mount
Shelf Mount
Height
(in/mm):
11.7/297 8.4/212
11.7/297 8.4/212
11.7/297 8.4/212
Width
(in/mm):
20/508 16.5/420
20/508 16.5/420
20/508 16.5/420
Depth
(in/mm):
9/229 12.5/317
9/229 12.5/317
9/229 12.5/317
Weight
(lbs/kg):
67/30.5 67/30.5
67/30.5 67/30.5
67/30.5 67/30.5
Front Panel Display (LCD):
2 x 20 Character LCD
2 x 20 Character LCD
2 x 20 Character LCD
Front Panel Indicators (LED):
Output Status & Alarm
Output Status & Alarm
Output Status & Alarm
Finish:
Dark Blue Powder Coat
Dark Blue Powder Coat
Dark Blue Powder Coat
Communication
Status Monitoring
4
:
Optional ESM/DSM
Agency
Safety Recognition:
EN 50091-1-2, IEC 60950, CB Scheme. CE
EN 50091-1-2, IEC 60950, CB Scheme.
Emissions:
EN 50091-2, CE Class A
Notes:
1
Batteries fully charged
2
Output regulation at nominal input frequency. Frequency variations will proportionally affect the output voltage (i.e., a 1% reduction in frequency will result in approximately a 1% drop in output voltage)
3
Varies with input line voltage and output load.
4
Status monitoring and embedded transponders are optional.