Major alarms, Minor alarms – Alpha Technologies VMX Series User Manual

Page 39

background image

39

017-940-B0-001, Rev. A

5.0 Operation,

continued

5.2 Smart

Display, continued

5.2.4

Alarm Indications, continued

Table 5-2, Major Alarms

Major Alarms

Active Alarm

Corrective Action

Probable Cause

Self-test FAIL*

1. Check batteries
2. Check inverter

• 36V battery string below 33.3Vdc
• 48V battery string below 44.3Vdc
• Inverter failure
• Batteries will not sustain load

LOW BATT VOLTS

1. Shutdown imminent
2. Check AC input
3. Connect generator

36V battery string below 33Vdc
48V battery string below 44Vdc

HIGH BATT VOLTS

1. Check charger settings

36V battery string above 45.0Vdc
48V battery string aboce 60Vdc

NO BATTERIES

1. Check battery breaker
2. Check connections
3. Check battery fuse

Absence of batteries detected
(alarm is inactive when battery capacity is set
to 0)

LINE ISOLATION**

1. Replace power supply

Line isolation has failed. All inverter operations
are suspended

OUTPUT FAIL

1. Check confi guration switches
2. Output overloaded?

The AC output has failed (check confi guration)

OUTPUT OVERLOAD 1. Check confi guration switches

2. Output short circuit?
3. Excessive load
4. Check output current

The VMX is overloaded

CHARGER FAILURE

1. Perform self-test

Charger has failed or shutdown, possible bat-
tery over-temperature

INVERTER TEMP

1. Check fan

Inverter heatsink has exceeded set temperature
(Standby operations are suspended until
temperature drops to safe level

CONFIG ERROR

1. Check confi guration switches
2. Check Inverter

The VMX is improperly confi gured. Operation is
suspended until error is corrected.

* To clear a Latched Self-test Fail Alarm, initiate and complete a successful self-test.
** Remove and replace VMX Power Supply. Do not try to clear alarm.

Minor Alarms

Active Alarm

Corrective Action

Probable Cause of Alarm

BATT TEMP PROBE

1. Check connection
2. Check sensor
3. Input connections

Remote Temp Sensor (RTS)
failed, or is not connected

INPUT FAILURE

1. Utility failure
2. Circuit breaker input

Utility AC input has failed

Table 5-3, Minor Alarms