017-940-B0-001, Rev. A

3. Make sure the battery breaker is off. After the batteries, battery connections, and battery

cables have been tested, plug the quick connects from the battery cable into the Battery
Input connection. The connector is keyed and color-coded to fi t in only one direction.

4. Plug the Remote Temperature Sensor into the Temp Probe connection. Route the sensor

end of the cable into the battery compartment, and attach it to the side of the center
battery.

5. If the optional LRI (Local and Remote Indicator) is included, connect the LRI terminal

block connections. Make connections to the auxiliary output if applicable.

6. If ESM or DSM status monitoring is used, plug the tamper switch connector into the 2-pin

TMPR connector on the front of the ESM.

6a. Connect the auxiliary output terminal block connections, if needed.

7. If using a Service Power Inserter, procede to Section 3.2. If you are not using an SPI,

connect the load to the Output 1-4 ± terminals on the terminal block and tighten clamping
screws.

3.0 Installation,

continued

3.1 Installation

Procedure

The VMX Power Supply has been designed for shelf mounting in the horizontal confi guration
or wall-mounting in the vertical confi guration.

1. Before installing the power supply, inspect for damage, loose connectors, or other

potential failures. Correct discrepancies before proceeding.

2. For horizontal confi gurations, place the VMX Power Supply on the appropriate enclosure

mounting shelf. The unit is placed in the lower-right compartment of PME enclosures, the
upper compartment of PWE, UPE, UPE/M Enclosures, and on the equipment trays of PN
Series enclosures.

For vertical confi gurations, mount the VMX Power Supply securely to a wall allowing for
plenty of space for connections and servicing (vertical dimensions in/mm: H 11.7/297 x W
20/508 x D 9/229).

Alpha enclosures are designed to properly vent the VMX Power Supply. If using a non-Alpha enclosure, it is
the customer’s responsibility to ensure the VMX Power Supply remains within its environmental specifi cations.

NOTE:

Batteries are an important part of the

VMX

Power Supply. Properly install and test all batteries,

battery connections, and battery cables before connecting to the power supply.

CAUTION!