beautypg.com

0 confi guration, 1 micro board setup – Alpha Technologies VMX Series User Manual

Page 26

background image

26

017-940-B0-001, Rev. A

4.0 Confi guration

4.1 Micro Board Setup

The Micro Board comes factory set, but the Micro Board switches are accessible should a
confi guration change be necessary. Setup details are included in this manual as an aid to
troubleshooting, and as a reference to verify confi guration. Only qualifi ed technicians should
perform reconfi guration. To access the Micro Board, remove the eight front panel Phillips
screws indicated.

Input Voltage (SW1-1): Factory set to order. Never change this setting.

Frequency (SW1-2): Factory set to match the ferroresonant transformer operating frequency
of either 60Hz or 50Hz. This setting should never be changed.

Output Current Rating (SW1-3 and SW1-4): Factory set. Output Current Rating is set to
match the model of the power supply. Never change this setting.

Fig. 4-1, Micro Board DIP Switch Settings

Dip Switch Location

Back of front panel

Factory set. Do not change settings.

OFF

ON

Vin, SW1-1

225V

115V

Freq, SW1-2

60Hz

50Hz

Iout

15A

22A

NA

NA

SW1-3

OFF

ON

OFF

ON

SW1-4

OFF

ON

ON

OFF