031-302-B0-001 Rev A

19

• Connection to utility power must be approved by the local utility before installing the power supply.

• Electrical codes require that a service disconnect switch be connected between the utility power source and

the Alpha power supply.

• Connection to the power supply must include an appropriate service entrance weather head.

ATTENTION

ONLY qualified personnel should connect the utility power. Power must be connected in

compliance with local electrical codes, and common safety practices must be observed.

WARNING!

2.0

Installation, continued

2.5 Connecting the Utility Power

Utility power enters the enclosure through an .875" knockout on the side or rear of the LPE. The

enclosure accepts a standard electrical fitting.

A “high-magnetic” trip circuit breaker must be used in order to accommodate the high-inrush currents

associated with the start-up of transformers (400A, no-trip, first-half cycle). Do not replace this circuit

breaker with a conventional service entrance circuit breaker. Alpha Technologies offers a high-

magnetic Square D circuit breaker and a BBX option (a UL Listed service entrance). Contact your

local sales representative for more information.

Description

Alpha Part Number

Square D Part Number

120V Installation — High-Magnetic (20A)

470-017-10

QO120HM

120V Installation — High-Magnetic (15A)

470-013-10

QO115HM

US BBX — External Service Disconnect

744-656-20

QO2-4L70RB

CAN BBX — External Service Disconnect

744-656-21

QO2-L70RB