Engine Control Module (ECM)

Power Node/ECM Certification

Power Node Location___________Node____________

Model#____________

Technician______________Date ____________

Serial #___________

Ignition Battery Check

(Record Results)

Verify correct Ignition Battery and Charger cables attachment ........................ Pass / Fail

Verify Battery Terminal surfaces clean, tight, and covered with

approved corrosion inhibitor (NCP-2) ........................................................... Pass / Fail

Battery Voltage Range 12.5-14.1Vdc. ........................................................... Actual= _____

Battery Charger LED is OFF when charge reaches 14.1V

and ON when discharge reaches 13.1V *See note 1 ................................. Pass / Fail

Verify Enclosure Fan Running? *See note 2 .............................................. Pass / Fail

ECM Interface Checks

Line sense Voltage. *See note 3

.................................................................. Actual = ________

Line sense Frequency Range 60Hz +/- 1Hz. ....................................................... Actual = ________

Verify all connectors correctly installed and locked into place. .................................. Pass / Fail

Run-Auto-Stop (RAS) rocker switch set to Auto. *See note 4 ............................ Pass / Fail

Verify Pad Shear Magnet is correctly installed. ....................................................... Pass / Fail

Verify Gas Detector is correctly installed. .............................................................. Pass / Fail

Verify Water Intrusion sensor is correctly installed. ................................................ Pass / Fail

ECM Alarm Verification

ECM has “Heart Beat”? *See note 5 ............................................................... Pass / Fail

Verify no Major alarms are reported.

............................................................... Pass / Fail

Verify the only Minor alarm reported is “Tamper” (Enclosure Door Open). ................ Pass / Fail

Water Intrusion Sensor (Hold float up to activate major alarm). ............................... Pass / Fail

Pad Shear Sensor (Place metal object between sensors to activate major alarm). .................. Pass / Fail

Gas Detector (Use a cloth moistened with Isopropyl alcohol to active major alarm). ............... Pass / Fail

Verify Line Failure Notification by disconnecting Line Sense. *See Note 6 ........... Pass / Fail

Verify DC Bus Fault alarm by disconnecting Battery Sense. *See Note 7 ........... Pass / Fail

Generator Functional Verification

(Record Results)

Verify oil clean and filled to capacity.

............................................................... Pass / Fail

Verify air filter clean and installed.

............................................................... Pass / Fail

Verify no oil leakage from oil filter, drain plug, and oil fill tube. ................................ Pass / Fail

Perform one minute self-test. *See note 4 ....................................................... Pass / Fail

Engine does not “hunt” excessively during idle/no load conditions. ........................... Pass / Fail

Enclosure properly grounding.

............................................................... Pass / Fail

Power Supply Verification

XMS2 Power Supply checked per section 5 of the operator’s manual ........................ Pass / Fail

Battery pack voltage (no load, generator off) range.

*See note 8, note 9

............................................................... Actual =________

Battery Terminals clean, tight, and covered with approved

corrosion inhibitor (NCP-2).

............................................................... Pass / Fail

Service Entrance, Enclosure, and Power Supply grounded properly. .......................... Pass / Fail

Successful completion of 10 minute Self-test. ........................................................ Pass / Fail

No Major or Minor alarms reported on XMS2 Smart Display. .................................... Pass / Fail

NOTES:

1. Some older 5kW chargers do not have an LED.

2. During initial installation, the fan will completely discharge the ignition battery if utility power is not

available.

3. The ECM can be configured for 120 or 240 VAC line sense. Refer to Section 4.4 of the ECM Manual for details.

4. Each time the RAS switch is placed in Auto, a one minute self-test is performed.

5. ECM’s built after 12/99 use a flashing SYS LED in lieu of the COM LED for the “Heart Beat”.

6. The generator will not start unless a line failure is greater then 10 minutes.

7. The generator will start immediately and run for a minimum of 30 minutes (Use RAS to stop Gen).

8. The difference between any battery in the string should not exceed 0.3 Vdc under load (XMS2 self-test).

9. Typical battery pack voltage ranges are 39.6-42.3Vdc, 52.8-56.4Vdc, and 105.6-112.8Vdc for 36/48/96 volt

systems, respectively.

Remove page and use for quick reference