Engine Control Module (ECM)

5.1

Self-Test

Generator testing can be initiated in four ways:

1.

The ECM can be programmed to periodically run an automatic test

(Default OFF).

2.

A Self-Test can be commanded via status communications.

3.

Momentary activation of the Engine Run command will cause the

ECM to effectively run a test. Note that this method is the least

desirable because the Self-Test Fail alarm will not be set if an

alarm condition arises.

4.

A one-minute automatic test is performed when the manual control

switch is returned to Auto from Stop.

Generator testing consists of starting and running the generator for a

programmable period of time (the default test duration is 10 minutes). The

ECM monitors all engine-related signals and will declare a self-test as failed if

any of the following alarms activate during the test:

Low Oil Pressure

Engine Over-temperature

Engine Over-speed

Engine Over-crank

Low Fuel

Alternator Over-voltage

ECM Control Failure

Alternator Not On

Low Ignition Battery

Low DC Bus Voltage

The ECM will not start a self-test if the engine is disabled, the stop switch is

asserted, or the engine is already running.

Section 5, System Self-test and Maintenance