Engine control module (ecm) – Alpha Technologies ECM User Manual
Page 41
![background image](/manuals/317442/41/background.png)
41
TM
744-862-C0-003 Rev.C
Engine Control Module (ECM)
5.1
Self-Test
Generator testing can be initiated in four ways:
1.
The ECM can be programmed to periodically run an automatic test
(Default OFF).
2.
A Self-Test can be commanded via status communications.
3.
Momentary activation of the Engine Run command will cause the
ECM to effectively run a test. Note that this method is the least
desirable because the Self-Test Fail alarm will not be set if an
alarm condition arises.
4.
A one-minute automatic test is performed when the manual control
switch is returned to Auto from Stop.
Generator testing consists of starting and running the generator for a
programmable period of time (the default test duration is 10 minutes). The
ECM monitors all engine-related signals and will declare a self-test as failed if
any of the following alarms activate during the test:
•
Low Oil Pressure
•
Engine Over-temperature
•
Engine Over-speed
•
Engine Over-crank
•
Low Fuel
•
Alternator Over-voltage
•
ECM Control Failure
•
Alternator Not On
•
Low Ignition Battery
•
Low DC Bus Voltage
The ECM will not start a self-test if the engine is disabled, the stop switch is
asserted, or the engine is already running.
Section 5, System Self-test and Maintenance