beautypg.com

Engine control module (ecm) – Alpha Technologies ECM User Manual

Page 27

background image

27

TM

744-862-C0-003 Rev.C

Engine Control Module (ECM)

3.1

Alarms Classifications, continued

Minor Alarm:

These alarms indicate a system fault which, though not indicative of

imminent system failure or shutdown, require service attention as the fault

condition could worsen to shut down the system. A site check by service

personnel is recommended.

MINOR ALARMS:

Control Fail (Latching - after 5 activations)

Indicates a control failure between the ECM and the generator set.

Typically this means that the engine did not start or stop when

commanded to do so. The alarm is cleared when the Reset

command is issued or when the manual stop switch is activated.

Alternator Off

This alarm is active if the generator controller has disabled the

alternator output. A generator controller may disable the alternator

output if the output voltage cannot be held above some threshold.

Self-Test Fail (Latching)

Status of most recent generator test. The alarm is cleared when the

Reset command is issued, the manual stop switch is activated or

another Self-Test command is issued.

Low Ignition Battery

Indicates that the generator’s ignition battery voltage has fallen below

11.5VDC. Alarm is cleared when battery voltage rises above 12.0VDC

indicating battery recovery has begun. Note that low ignition battery

voltage is not alarmed during engine cranking.