beautypg.com

Start delay, Current limit/short circuit protection, Power limiting – Alpha Technologies Cordex 48-1kW 23 4000W User Manual

Page 26: High voltage shutdown (hvsd), Battery eliminator operation

background image

Argus Technologies Ltd.

010-566-C0 Rev C WC

Printed in Canada. © 2005 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 4 of 11

2.10 Start

Delay

The modules are equipped with a delay timer in order to stagger start a series of modules to prevent excessive
loading of generators upon start up. The built-in timer delays the turn on of the module depending on the value
selected (up to 120 seconds) via the CXC. A minimum one-second delay is preset to allow charging of the input
capacitors.

2.11 Current Limit/Short Circuit Protection

The current limit function determines the maximum output current limit of the module, regardless of output voltage
or power. Maximum output current is limited to a constant value down to short circuit condition. Current limiting
can be used to mate the rectifier output current ampacity to the needs of the load and parallel battery to minimize
excessive battery recharge current.

The rectifier will sustain a short circuit at the output terminals indefinitely. The maximum short circuit current shall
not exceed 105% of the rated full load current.

2.12 Power

Limiting

Each module is designed to limit power output to the module specification. This enables more current to be
supplied at lower output voltages, and allows matching of output to the demand of constant power loads, normally
seen with telecom equipment.

This feature may also be used for a faster recharge of flooded batteries paralleled with the load.

NOTE: Current limiting overrides the power-limiting feature.

2.13 High Voltage Shutdown (HVSD)

This feature provides protection to the load from over voltage conditions originating from the rectifiers. It operates
by shutting down the offending rectifier module when a high output voltage condition occurs. Indication is through
the red Alarm (Module Fail) LED. Modules will restart automatically; however, if more than three over voltage
conditions occur in one minute, the module will latch off and remain shut down until it is reset via the CXC.

2.14 Battery Eliminator Operation

Modules maintain all specifications (except where indicated) with or without a battery attached in parallel to the
output; however, if a battery or another module supplying DC voltage in parallel is not present, there will be no
monitoring or control activity if there is an AC power failure or input fuse failure.