beautypg.com

Cxcm battery –48v connection, 13 analog inputs for cxcm, 1 voltage – Alpha Technologies Cordex 48-1kW 23 4000W User Manual

Page 15: 2 current, Caution: to reduce risk of fire, use only 0.129mm

background image

A

RGUS

T

ECHNOLOGIES

C

ORDEX

48-1

K

W 23" S

HELF FOR

S

YSTEMS UP TO

4000W

WITH

D

ISTRIBUTION

CAUTION: to reduce risk of fire, use only 0.129mm

2

(#26 AWG) or larger wire.

Terminal

Description

Default Name

Signal Type

Range

21-22(common)*

Alarm Output 2

LVD2

NC/COM/NO (JP2)

60VDC / 1A

19-20(common)*

Alarm Output 3

LVD3

NC/COM/NO (JP3)

60VDC / 1A

17-18(common)*

Alarm Output 4

System Minor

NC/COM/NO (JP4)

60VDC / 1A

15-16(common)*

Alarm Output 5

System Major

NC/COM/NO (JP5)

60VDC / 1A

13-14(common)*

Alarm Output 6

AC Mains Hi-Low

NC/COM/NO (JP6)

60VDC / 1A

11-12(common)*

Alarm Output 7

Not assigned

NC/COM/NO (JP7)

60VDC / 1A

9-10(common)*

Alarm Output 8

Not assigned

NC/COM/NO (JP8)

60VDC / 1A

23-25**

Alarm Output 0

System Fail Output

NO/COM/NC

60VDC / 1A

E1

Battery -48V

Battery -48V

Neg (-)

20—60VDC

J3

Ethernet Port

Ethernet Port

N/A

N/A

P1

LVD Control

LVD Control

Polarized

0—60V / 1A

P5, 1-2***

Digital Input 1

Distribution Fuse (Alarm)

Pos (+) or Neg (-)

0—60VDC

P5-3, P6-1***

Digital Input 2

Distribution CB (Alarm)

Pos (+) or Neg (-)

0—60VDC

P6, 2-3***

Digital Input 3

Battery CB (Alarm)

Pos (+) or Neg (-)

0—60VDC

P7

Voltage Input 1

Discharge Voltage

Pos (+) or Neg (-)

0—100VDC

P8

Current Input 1

Discharge Current

Pos (+) or Neg (-)

±50mV

L120 L124

L120 L124

1-2****

General Input 1

Temp

Probe #1

Voltage

#3

Pos (+) or Neg (-)

0-20VDC

0-60VDC

3-4****

General Input 2

Temp

Probe #2

Voltage

#4

Pos (+) or Neg (-)

0-20VDC

0-60VDC

5-6****

General Input 3

Not

Used

Voltage

#5

Pos (+) or Neg (-)

Not Used

0-60VDC

7-8****

General Input 4

Bipolar

Voltage

Temp

Probe #1

Pos (+) or Neg (-)

±60VDC

0-20VDC

Table B–Wiring connections for CXCM

*

Jumper selectable NO or NC Form C contacts. Can be configured to de-energize on alarm (DOA) of energize on alarm (EOA).

**

System Fail output relay is fail-safe and will de-energize during an alarm condition.

***

See Table D for definitions of logic and system.

****

Bipolar (Voltage Input) is ±60VDC, Voltage (Input) is 0—60VDC, Temp Probe is 0—20VDC with power source.

To aid the user with installation, frequent reference is made to drawings located at the rear of this manual. Custom
configurations may be detailed within the Argus power system documentation package.

4.13 Analog Inputs for CXCM

CAUTION: Ensure the correct polarity is used for all input cable terminations.

The analog input channels are used to monitor various types of electrical signals. Some of the analog channels are
reserved for specific signals, while others are designated as general-purpose inputs, which accommodate various
types of analog signals. The input cables should be bundled together and routed through the entry holes of the
shelf, if applicable.

4.13.1 Voltage

Voltage Input #1 (discharge voltage per CXC software) terminals on the shelf provide connections to an optional
secondary voltage input. For example, this can be terminated to the load side of an LVD contactor to monitor load
voltage.

Voltage Input #2 (charge voltage per CXC software) is wired internally to the rectifier output voltage of the shelf.
This is used as the reference for system alarming (such as high voltage) and control (such as low voltage
disconnect).

4.13.2 Current

Current Input #1 terminals provide connections (factory-installed) to the system current shunt normally used to
monitor discharge (load) current.

030-704-C0

R

EV

A

P

AGE

9

OF

14