Installation

Terminal assignment

X3/

3

Signal

type

Function Level

X3/62 Analog

output

Output frequency

0 ... + 6 V

X3/7 -

GND1, reference potential for analog signals -

X3/8 Analog

input

Setpoint input Change setpoint selection
range via DIP switch

0 ... +5 V (default setting)
0 ... +10 V
0 ... +20 mA

X3/9 -

Internal, stabilised DC voltage source for
setpoint potentiometer

+5,2 V (ref.: X3/7)

X3/20 -

Internal DC voltage source to control digital
inputs and digital outputs

+20 V ± 10 % (ref.: X3/7)

HIGH START

X3/28 Controller

inhibit

LOW

STOP

X3/E1 Reset

fault

(TRIP−Reset) HIGH

Reset fault

HIGH Switch−off with fault indication

"EEr"

X3/E2 External

fault

LOW

No fault

E3

E4

X3/E3

34 Hz (2000/min)

HIGH

LOW

67 Hz (4000/min)

LOW

HIGH

X3/E4

Digital
inputs

Activation of fixed speeds
Adjust maximum frequency C0011 in order
to go through the complete speed range.
Maximum value of C0011 = 87 Hz (5000/
min)

50 Hz (3000/min)

HIGH

HIGH

X3/39 -

GND2, reference potential for digital signals -

X3/A1 Digital

output

"Pulse inhibit active" message

HIGH pulse inhibit active

+20 V Internal voltage source (jumper to

X3/20)

X3/59 -

DC supply for X3/A1

+24 V External voltage source

ON

OFF

n_e2fcx070

Switch

position

Signal

at

X3/8

1 2 3 4 5

0 ... 5 V (default
setting)

OFF OFF ON OFF OFF

0 ... 10 V

OFF OFF ON OFF ON

0 ... 20 mA

OFF OFF ON ON OFF

Fig. 20: Switch position control terminal module